详细说明:TDK-Lambda EWS3000T系列 单体式电源(使用说明书)pdf,TDK-Lambda EWS3000T系列 单体式电源(使用说明书)3. TERMINAL CONNECTIONS
3-1 When Remote Sensing and ON/OFF Control Are to Be Used
3-phase
+s爬
200 input
TrIPUr
o)。c
Q。a。感
COl
P888
Control
Load
rM‖ Relay or TtL
ooad
aDd
kDTr
HIPUT3. AC70n-740V
Ground
0.50l4A
上网回
when a fixed-voltage power supply is to be used, the REF and PV terminals should be shorted together
sing the short piece supplied
(A short piece has been inserted between the REF and Pv terminals prior to shipment
3-2 When Remote Sensing and ON/OFF Control Are Not to Be User
when no remote sensing is needed short the
+5 terminal with the output terminal, and
the -s terminal with the -output terminal
respectively, using the twisted wires supplied.
pto
+
Load
CNT
tcuT3粪nz00a4nV
Ground
5.EDr1晶
Art IN
When no oN/OFF control is needed, short the
ToG terminal with the cNT termInal, using
the short piece supplied
Be sure to connect the remote sensing terminals. otherwise, the overvoltage protection circuit aclivaley
to shut off the output
.When a fixed-voltage power supply is to be used, short the REF and PV terminals together, using the
short piece supplied.
(A short plece has been inserted between the REf and Pv ter rnirals pr ior to shipment J
800082
4. DESCRIPTION OF THE FUNCTIONS AND PRECAUTIONS
4-1 Output Voltage Adjusting Procedure
The output voltage setting can be changed by adjusting the output voltage trimmer
pot (vAD))on the front panel. Turning the trimmer clockwise increases the output
voltage. the output voitage setting should be within +% of the rated output
voltage value
4-2 Remote Sensing Function
This function is used to compensate for a voltage drop(line drop) due to the wiring
between the power output terminal and the load terminal. the line drop
compensation vol tage should be within +% of the rated output voltage value and
be lower than the maximum output power value given in the power supply output
power specification. As to the remote sensing wires, use shielded wires or twisted-pair
w『es
When the remote sensing function is not to be used short the +s terminal with the
output terminal and the -S terminal with the- output terminal respectively, using
the sensing wires supplied
4-3 ON/OFF Control function
The output voltage can be turned on or off by an external signal without turning on
or off the input power Shorting the toG and Cnt terminals together turns the
output on, and opening these terminals turns off the output. When this function is
not to be used, short the terminals together using the short piece supplied
Note that the terminals have been shorted by a short piece prior to shipment
Specifications and Functions
1. It is TTL compatible. The maximum voltage applied to the cnT terminal shall be
less than 30V and the reverse voltage be less than-07 V. The control signal driver
sink current shall be less than 3. 5 mA
CNT level with
3,5mA
reference to tog
Power outpu
CNT
Sink current
L(0.8V or less
ON
TOG
Relay transistor, or TTL
30000+2
2. Control can also be exercised by opening or closing the contacts(switch, relay )or
by turning the transistor on or off. (TOG-CNT shorted: Output ON, TOG-CNT
opened: Output OFF)
3. Since the circuit is isolated from the input/output circuit by a photocoupler,
control can be easily performed, independent of whether the power output is
positive or negative. the tog terminal should be connected with the gnd of the
control circu
4-4 Overcurrent Protection(Delay Shutdown OCP)
If an overload or shorted condition occurs and continues for more than five seconds
the output is shut off to protect the power supply and the load. To restore the output,
it is necessary to shut off the input momentarily and, then turn on the input again. (as
for the overcurrent detection time the pf signal duration is detected.
If the unit leaves the overload condition within the specified time interval, the output
automatically restores to normal
4-5 Overvoltage Protection(Tracking OVP)
This unit incorporates an output shut-off manual reset type overvoltage protection
function. If the output voltage exceeds the specified voltage value, this overvoltage
protection function is performed to shut off the output. To restore the output, it is
necessary to shut off the input momentarily and, then turn on the input again
Since an automatic tracking system is employed, the overvoltage protection detection
point follows the set output voltage so as to perform a protection, according to the
output voltage, at all times. It should be noted that the overvoltage protection
detection point is fixed and cannot be changed. ihe a valte of the specified voltage
"Vo+a"(5 v type: 5V+1.0 to 2.0, OVP value: 6.0 to 7.0 V for 5 V output) is fixed
when the set output voltage is V1.V,+a "is automatically set as the oVP detection
point
4.6 Over Temperature Protection
This unit incorporates an output shut-off manual reset type over temperature
protection tunction. It the ambient temperature or the temperature inside the power
supply exceeds a certain limit (detection temperature: 120C+ 10%), this function is
performed to shut off the output. to restore the output after it is shut off by the over
temperature protection, it is necessary to shut off the input and after the
3000g2
temperature falls, turn on the input again. When the output is shut off, a PF signal is
indicated
4-7 Built-in Fan Stop Detection
The three cooling fans incorporated in the power supply are monitored for proper
operation If even one of the fans stops, the power output is shut off. At the same
time a pf signal is indicated
4.8 Low Input Voltage Detection
If the input voltage lowers to 140-165 VAC, the output is shut off. When the input
voltage restores to normal, the output automatically recovers.
4-9 Low Output Voltage Detection
If the output voltage lowers to 75% to 80% of the set voltage value due to an input
voltage drop, instantaneous power failure, or output overcurrent protection, the PF
(power fail signal goes to the H" level to indicate the occurrence of an output
abnormalit
Since an automatic tracking system is employed, the low output voltage detection
point follows the set output voltage so that a detection point suited to the output
voltage may be set at all times. The detection point is fixed and cannot be changed
The specified value"Vox% to 80%"is fixed. If the set output voltage is v1
V1x75% to 80%"is automatically set as the detection point
The Pf signal is an open collector output, and it is isolated from the input/output
circuit by an photocoupler
PF VE MAX= 30V
Fc: MAx- 20mA
TOG
4-10 Input Open Phase Detection
If one of the 3-phase input lines becomes open, or if one phase voltage falls below 160
VAC the output will be shut off in about five seconds
To restore the output to normal, once shut off the input and, after a while, apply a
normal input line voltage again
B008-2
4-11 Output Ripple
The maximum ripple voltage(including noise)given in the specification is the value at
the power supply output terminals. If the load wire is long, the ripple at the load end
may be excessive unless an electrolytic/film capacitor is connected to the load end. It
should also be noted that an accurate measurement cannot be made if the ground
lead of the oscilloscope probe is too long
4-12 Input Surge Current Suppressing Function
This unit incorporates a thyristor-based input surge current suppressing circuit. if the
input power is removed and reapplied within five seconds, this function will not be
performed due to the retention characteristics of the thyristor
When two or more power supplies are to be used, the setting of the input switch and
the selection of an external fuse should be carefully made. For information on the
input surge current suppressing circuit, switch, etc, refer to the Nemic-Lambda
general catalog.
EwS 3000 Input Surge Current Waveform
(Input: 200 VAC, in put phase angle: 90, load
100%, ambient temperature: 25C)
20A/DIV50mS/DIV
4- 13 Line Filter Ground Terminal (ACG Terminal)
The aCG terminal on the front panel is connected with the ground midpoint of the
line filter circuit incorporated in the power supply. When the power supply is to be
used as a single unit short the ACG ter minal with the fg terminal, using the short
piece supplied.
When two or more power supplies are used, the leakage current increases accordingly
To reduce the leakage current, remove the short piece between the ACG and FG
terminals. Further, to minimize noise install a noise filter on the input line side
B0008-2
Ac 1)
RI ER3
AC2)
ACG
R1 R2. R: Bleeder resistor
ACG
FG
F
FG
FG
AC
ACinput
e
4-14 Parallel Connection
Parallel connection of units can be used either(a)to increase the output current or( B)
to use one unit as a back-up power supply
(A)To increase the output current
This power supply is provided with a current sharing function. with this function.
up to five units can be operated to provide nearly uniform output currents, while
monitoring each others output currents
(a) To use the current sharing function, connect the PC terminals of the power
supplies with each other.
(b)Set the same output voltage.
(c) Use the same output load wires
(d) For each unit, the output current should not be more than rn% of its rated
output current value
Power supply
Load
800082
(B) To use one unit as a back-up power supply
Two supplies (one being a back-up)can be used for one load to improve the
reliability of the system
(a)Set Lhe same output voltage.
b)Use the same output load wires.
(c)The power supply output voltage should be increased in consideration of the
diode forward voltage drop(va)
(d) The power supply output voltage and output power should be within the
ificatio
Output power(w)=(Vo+ve) lo
Power supply
v
e
) Vo +V
4-15 Series Connection
Series connection of units can be used either(A) to increase the output voltage or ( B)
to use them as t power supplies
Power supl
Power supply
° utput
terminal
terminal
Load
output
terminal
(B)
30008-2
4-16 Master-Slave Operation
Two or more power supplies can be connected in parallel so that one unit(master
power supply) may control the output voltages of the other units (slave power
This function can be used only when the power supplies are of the same type (up to
five units).
(a) To use the current sharing function, connect the pc terminals of the power
supplies with each other.
b)Connect the Pv terminals of the power supplies with each other.
(c) Connect the REF and pv terminals of the master power supply
(d) Use the same output load wires.
(e) for each unit, the output current should not be more than 80% of its rated output
current value
Power supply
⊕
PC
Master
Load
REF
PC
REF
PC
Slave
PV
0008-2
10