Introduction
Thank you for purchasing the Toshiba High-Performance Inverter"TOSVERT VF-A5"
The"VF-A5"inverter has many various functions built in for use with a 3-phase induction motor. All
Operations of this unit are done via the easy-to-use keyboard-type operation panel. A blind function
(Refer to page 55)that displays only those functions required for operation, and an edit function(Refer to
page 34)that automatically collects parameters that differ from their default settings are used to make
basic operation and setting easier. Advanced control technology features (sensorless vector control
feedback control, current limit, retry, and stall prevention functions) are built in, so that the inverter will not
trip easily, and will provide unparalleled reliabilty
Please read this manual thoroughly before use to properly understand the correct use of the outstanding
functions of the "VF-A5'
This manual should be stored by the user of the"VF-A5 for reference during maintenance and inspection
Symbols used in this manual are as shown below. Understand them before reading this manual
1. LEd display character codes: Reter to page 131
2. To indicate a parameter display on the operation panel in this manual:
P
Example sCC日
To indicate a panel key
Example LENTER key
The box l is not used when indicating parameter group names and parameter settings
Note)The box L is not used when displaying parameters in tables
E658051
Table of contens
1. Acceptance Inspection and Precautions
2. Installation Precautions
3. Extemal View and Component Names ..,.
peration Precautions .
5
5. Wiring Precautions
6. Standard Connections
15
6.1 Standard Connection Example
15
62 Terminal Functions……18
7. Operation and Adjustment
。b看·鲁鲁看
7.1 Operation Panel
32
7,2 Basic Operation…;
7.3 Operation Modes…
37
7. 3. 1 Standard Monitor Mode
37
7.3.2 Status Monitor Mode
7. 3. 3 Setting Monitor Mode
41
7.3.4 JOG Run Mode
7.4 Operation Mode selection
45
7.4.1 Operation Mode Changeover
742 Run/Stop Command[Ceir是]…………45
7.4.3 Frequency Command Source Setting Function
FHEid in Lir.Lik
45
4.4 Parameter Setting Function[ FHie in ErLik]
46
7.4.5 Standard Parameter Value Reset Function
[k≌尸inp]…47
7.4.6 Selection of Stopping Method from the pane
48
7.4.7 Fault reset
8. Parameter Explanations
50
1. ErF V/f settings
50
V/f pattern①
51
V/f pattern②
52
Acceleration/deceleration time settings
53
Acc/Dec patterns, AcC/Dec pattern adjustment,
LoW/High
54
Blind function selection
55
Upper limit/lower limit frequencies
Reverse operation disable selection
56
E6580516
2. ir.Fr" Acc/dec#1and# selection…………………………………………57
Pane| feedback contro…………………………
58
Panel reset selection
...·.·.“··:··=··=·=;
58
Fundamental parameter switching
59
3. Er.St Input terminal selections (1
60
Input terminal selections(2
61
Output terminal selections (1
62
Output terminal selections 2
63
Low speed, acceleration/deceleration
complete, speed reach output signals
64
nput/output terminal response time selections
55
Commercial power/INV switching
…-66
Output terminal pulse frequency selection
67
RR input special function selection
67
4. Ers Run frequency col
68
Start-up frequency/End frequency --............................69
Jump frequencies…
70
PWM carrier frequency……
5
SF Preset speed operation (1
72
Preset speed operation (2)
Frequency priority selections
74
Jogging operation
75
Frequency setting input signal characteristics
76
6. Er"F,- Electronic thermal protection (1
Electronic thermal protection (2)
DC injection braking settings (1
DC injection braking settings( 2)
81
Dynamic braking operation
82
Emergency stop
83
Retry function
83
Regeneration power ride-through control
84
Auto- restart…………………………
Trip function selections
85
Output short circuit detection selection
85
Fault trip saving…
7.5- Fk Pattern run①
87
Pattern run②
88
E6580516
8. Eir.Lt Panel operation permission
89
Industrial application parameters selection
90
Standard setting mode selection…………90
Command/ frequency mode selections
Status monitor display selections
92
Blind function selection
92
Units settings
93
9. rff Meter adjustment parameters
94
9. Device Specifications
95
9.1 Model and standard Specifications
95
92 External Dimensions……………………………………
99
10. Options
103
1. Error displays and Troubleshooting
105
11.1 Inverter Trip causes and remedies
105
11.2 Other Fault Troubleshooting -----
109
12. Maintenance and Inspection…………………110
12.1 Preventive Maintenance and periodic Inspection
110
12.2 Component Replacement
········“
111
13. Storage
112
14. Warranty
112
Appendix
Appendix table1. Parameter list……
113
Appendix Table 2. List of trip
129
Appendix Figure 1. Input terminal information
130
Appendix Figure 2. Output terminal information
130
Appendix figure3. Character codes∴………………………131
Appendix Table 3. Standard default settings per inverter capacity
132
Appendix Table 4. Industrial application parameters
133
Appendix Table 5. Changed settings memo
E6580516
1. Acceptance Inspection and Precautions
(1) Confirm that the unit has not been damaged during shipment
(2)Confirm that the model noted on the rating nameplate is as ordered
3)When storing the unit temporarily after purchase, store it in dust-free, well-ventilated location
(4)Special care is taken during product manufacturing, packaging, and shipment. If any problems are
discovered, however, please contact your dealer immediately.
Detailsof rating nameplate
TRANSISTOR INVERTER
a TYPE-FORM VEA5-2037P
Inverter model
Applicable
SOURCE 200-220V-50H2 FREQUENCY 0.1-80Hz -Rated output frequency
power source
200-230V560Hz
(0.01-400)H
Capacity
CAPACITY 6.5 KVA CURRENT
165A
Rated output current
Rated output→- VOLTS
200-230V AC MOTOR 3.7 KW MAX
voltage
Applicable motor capacity
LOT NO. i
M6584991P
MADE IN JAPAN
Details of model no
Model n
tion PcB
Type
Model
specification
VPA同S-O|3|7P冈-A|2|2
Model name
Standard
Additional
motor
functions
Option PCB and special specification codes
TOSVERT
capacity
口口: Special specification code(口口are
VF-A5 series
E: Fully enclosed[ M: 12-bit binary input PCB 4526A install numbers
A: General pur
04kW:004
F: External
Q: Expansion terminal block PCB 45 14A installed
pose high-
075kW:007
heatsink
R: Expansion terminal block PCB 4514B installed
performance
15kW:015
N: GTR7
22kW:022
odification
S: Expansion terminal block PCB 4514C installed
37kW:037
T: Expansion terminal block PCB 4514D installed
Input voltage
55kW:055
J: Expansion terminal block PCB 4515A installed
2:200v-230V
75kW:075
1(nonstandard) K: ExDanso terminal block PCB installed
lone: Standard
4:380-460V
11kW:110
D: Expansion terminal block PCB 4515C installed
8: DC power source
15kW:150
V: RS485 communication PCB installed
TOSLINE-F1oM communication PCB install
input
185kW:185
(200V class output)
22kW:220
Operation
X: TOSLINE-F20 communication PCB installer
panel
9: DC
30kW:300
37kW:370
P: Installed
B: Not installed
(400V class output
UL-listed: UP. UB
75
90kW:900
110kW:11
132kW:132k
160kW:160k
220kW:220k
280kW:280k
E6580516
2. Installation Precautions
This inverter is an electronic control unit. Take special care concerning the installation environment
Confirm that the input power is within +% of the rated value If the input power voltage range
tolerances are exceeded during use, the protective circuits may function or the inverter may be
damaged
Avoid installation in hot and humid locations
Use the unit within an ambient temperature of
where condensation or freezing may occur, or
-10to40℃
where water, dust, or metal chips may come into
Because the inverter radiates
contact with the inverter
2动线
heat, when installing in a
· Install in a location
d panel take special care
free of corrosive gases
concerning ventilation and
E/
or cutting fluids, etc
panel space. Removal of
the cover is recommended
10℃
using in a pan
ensure maximum longevity
and reliability.
Do not install the unit
The inverter may malfunction if the
locations that
following types of devices are
experience large
stalled nearby, so use proper
vibrations
precautions
Solenoid
Install a surge kill
Brake
the exciting coil
Electromagnetic
Resistor
contactors
Fluorescent lights
Resistors
Keep away from the inverter
Ground the g/E
Attach the unit to a non-combustible material such as a metal panel. to
terminal to prevent ensure adequate ventilation, maintain the following installation spaces, and
electrical shock and
always install the unit vertically in the longitudinal direction. When installing
malfunction due to
multiple inverters in a row, leave a clearance of
noise
10cm or
at least 10cm between each unit this clearance
more can be reduced depending on the environment
5cm or
more
5cm or
or by adding fans
more (For 37kW and larger units, leave a clearance of
at least 20
re and below the inverter to
10cm or more allow for fan replacement and wire bending
space.
Contact the Engineering department for furthe
details
Inverter life depends greatly on the ambient temperature make sure
that the ambient temperature of the installation location dose not exceed the
Measure the temperature at the positions shown in the diagram on the right, tcm
maximum ambient temperature rating(40C)
会|5cn
and confirm that it is less than the maximum ambient temperature rating
Measurement
40C).(50C or less when the cover is removed.
22kW and larger units can be used up to an ambient temperature of 50C
(Do not remove the cover from 22kW and larger units
Measurement
position
x Always install the inverter in the longitudinal direction on a vertical surface
E6580516
3. External view and component Names
3.1 Component Explantion (I)
d Cooling air exhaust port
⑥ Mounting hole4 holes)
⑤ Upper caution sticker
⑦ Mounting bracket
⑥ Chassis( plastic
① Operating pane
⑨ Ventilation slots
② ROM interface window
d Optical cable access slot
semi-transparent
for installation of optical
communication options
③ Front cover wamings
① Finger clasp for
(I)
removIng cover
① Rating nameplate
(I)
白I)
1(12 Cooling
④ Cover(astl
Wiring access plate
Always cut out the wiring
pons as necessary.
an 11kw or larger unit,
te rubber bushing
or a knife as
OOperating panel:removable
hown below
Refer to section 3. 3 Removal of operating panel
2 ROM interface window: removable
Rubber
Refer to section 3. 3 Removal of ROM inetrface window
bushing
④ Cover
5 Upper caution sticker
Always read the cautions on the tront of the cover and remove
Always remove this sticker when the ambient
the cover when wiring
temperature is high
Refer to section 3.2 Removal of cover
⑨ Ventilation slots:
If the ambient temperature of the inverter unit exceeds 40C when
A cover-up plate option is available for fully-sealed
mounted in a panel, remove the cover the unit can then be used
applications.
up to a temperature of 50C
3.2 Removal of cover
1)For 7.5kW and smaller. Place your fil
on the finger clasps for removing the cover shown in the 3. 1 Component Explanation
(Drawing
force in the direction of the aows(I), and pull the cover up in the direction of arrow
e covel
2)For 11-18.5kW. Remove the two screws on the cover wiring inlet, and then remove the cover like the 7. 5kW models
2)For 22*W and larger- Wait for the"CHARGE"lamp on the cover(sheet metal to go out. then remove the four screws holding
the cover(six screws for 37kW and larger), and the cover will come off
Hook structure
Fitting structures
仓(I)
广|m
E6580516
3.3 Removal of the rom Interface
Window and operation Panel
KLV
Operation panel
RUN LSTOP
(Ⅳ)
SET
(I)
USH
ROM interface window
( Press where the word PUSH is located
(I) The operation panel attachment
screw can now be seen Turn it
The top of the window will open
in the direction of the arrow
I)unit it completely
(I)Hold the top of the window, an
loosens
pull it out in the direction of
(M) When the screw has
the arrow(
completely loosened, pull the
operation panal out in the direction
of the arrow(v)
3.4 Component Explantion(1)
Option connector
(40-pin)
② Operation panel
RS232C communicationN
connector
onnector
(Modular 6-pi
Option ROM socket、
② Operation panel
attachment stud
⑨ ROM cover
26 Changeover switch for
frequency setti
signal inputs
V terminal i/ changeover switch
口‖ RX terminal10V/5 changeover switch
2)Option connector
(20-pin)
②
日
Control terminal block
囵圈圈
② Flat cable
_啊备
(for control terminal block)