详细说明:力特 有效保护变压器和控制变压器的重要性—变压器保护(英文)pdf,力特 有效保护变压器和控制变压器的重要性—变压器保护(英文)Transformer Protection Basics
Expertise AppliedAnswers Delivered
Table 1.
Fuses for transformers over 600 volts
For more specific sizing recommendations, refer to Tables
Maximum Fuse Rating in Percent
4 and 5 for Class j fuse protection and tables 6 and 7 for
of transformer Rated Current
Class cc fuse protection
Transformer
Primary
Secondary Fuse Rating
Rated
Fuse Rating
600 volts600volts
Table 4 shows recommended Class J fuse ratings
Impedance
Over 600
or less in
or less in
for standard transformers below 600 Volts without
600 volts in
Volts
all locations unsupervised supervised
secondary protection, while Table 5 shows the similar
locations
ocations
recommendations in applicatians with secondary protection
Not more than
6%
300%
250%
125%
250%
Table 4
More than 6%
Class J fuse Protection Of Standard Transformers Without Secondary
nd not more
300%
225%
125%
250%
Protection--230, 460, 575 Volts Single-Phase
than 10%
NEC and UI Maximum Allowable Fusing iamps)With anly Primary Protection
1. Littelfuse IDSR, LLNRK /LLSRK/LLSRK ID, FLNR ID/FLSR ID, and JTD ID series
230 Volts
460 Volts
575 Volts
time-delay fuses may be rated at 125% of transformer secondary current
Single-Phase
Single-Phase
Single-Phase
2. Where the required fuse rating does not correspond to a standard fuse rating
Primary JTD or Primary JTD or Primary JTD or
the next higher standard rat ng is permitted
3. An individual primary fuse is not required if the primary circuit fuse is not
Transformer Current JTD ID Current JTD_ID Current JTD_ID
kVA
(A) Series (A) Series A
Series
greater than 300 of transformer primary current
0.15
065112033810026KLDR3/
035
1.52
0.76
0.61
1-1/2
Transformers Rated 600 Volts and less
05
2.17
310930721/2
UL Industrial Control Standards(No 508) and motor
业电
075
100
4.35
6
Control Center Standards(No 845) specify control power
2.17
1.74
150
6.52
10
3.26
ransformer protection corresponding to NEC Article
200
8.70
12
4.35
63485
430.72(C). In addition UL requires the primary of control
250
10.87
15
543
4.35
powertransformersusedincontrollershavingshort-circuitwww.3000113.04(171216.52105.228
350
15.22
20
761
12
6.09
10
UL Class CC, J, R, or T fuses. For maximum fuse ratings
500214301087158:7012
permitted by the nec, refer to Table 2 for sizing of primary
800
45
13911712
fusing and table 3 for sizing of secondary fusing
y+:010=0)们21352
Table 2
Maximum Acceptable Rating of Primary Overcurrent Device
Fuse recommendations are based on maximum acceptable rating of prima
fuse as per NEC 450.3(/, UL 508 32.7, and UL 845 11.16 and 11.17, as sum
Rated Primary Maximum Rating of Overcurrent Protective Device
marized in Table 4A below.
Current Amperes
of Transformer Primary current Rating
No secondary
Secondary fusing provided
Table 4A
fusing provided
accordance with Table 7
Less than 2
300
Rated Primary
Maximum Rating of Fuse %o of Transtormer
2 to less than 9
167
Current Amperes
Primary Current Rating
(No Secondary Fusing Provided)
9 or more
125
250
Less than 2
300
Table 3
2 to less than g
Maximum Acceptable Rating of Secondary Overcurrent Device
C ar
125
Rated Secondary Maximum Rating of Overcurrent Protective Device
2. If 125% does not correspond to a standard fuse rating, the next higher s andard
Current Amperes
% of Transformer Secondary Current Rating
rating may be used
Less than g
KLDR= Littelfuse UL Class CC time-delay serie
g or more
1252
1. 500 for Motor circuit control power transformers
2. If 125% does not correspond to a standard fuse rating the next higher standard
rating may be used
Reference NEC 430.72(c) Exception No. 2: 450.3(b) 1 and 2 UL 508 32. 7: 845 11.16
nd1117
C 2010 Littelfuse POWR-GARDQ Products
ww. littelfuse com
Transformer Protection Basics
Expertise AppliedAnswers Delivered
直目目里目
Table 5
Class j Fuse Protection Of Standard Transformers with Secondary
Table 6 shows recommended Class cc fuse ratings for
Protection-230, 460, 575 Volts single-Phase
transformers with single-winding 240 Volt primaries while
NEC anc UL Maximum Allowable Fusing amps) With Secondary Protection
Table 7 shows similar recommendations for transformers
230 Volts Single Phase 460 Volts Single-Phase 575 Volts Single-Phase
with single-Winding 480 Volt primaries
JTD or
JTD or
kvA Current(A) JTD ID Primary TD In Primary
Table 6
Series Current(A)JTD_ID
Series
Class cc fuse Protection Of Transformers With single-Winding Primaries-
0.15
0.65
1-1/2
033
8/10
26
KLDR 3/4
240 Volt Primary
0.76
061
1-1/2
NEC and UL
Littelfuse
Maximum Allowable Fusing(amps) Recommended
087
212
With Only Primary Prote ction
0.75
3.26
130
4.35
1021761745
Transformer
Primary
Control Power
Standard
Time di
Current(A) Transformer
Transformer KLDR Series
261
0.10
1/2
0
2.00
8.70
4.35
10
8
0.21
1087
5.43
1-12
10
657
0.42
1522
17-1/2
609
21745010972587020
54
21/2
1-6/10
8/10
5.00
63
18/10
40
13.91
80173401435
200
0.83
2-1/2
1-1/2
1000
4348
100
21
1739
业电
250
04
已30012561431/2
2-1/2
KLDR- Littelfuse UL Class CC time-delay series
1.46
4-1/2
Fuse recommendat ons are based on maximum acceptable rating of primary fuse as oer nec
3-12
3-1/2
3-1/2
450.3(b UL 508 32 7, and UL 845 11.16 and 11. 17, as summarized in table 53 below
3.13
5-7/10
57/10
Table 5B
公可网:wW,
93
10
10
Rated Primary
Maximum Rating of Fuse of Transformer
These fuse ratings permissible only when secondary protection is provided in accordance with
Current Amperes
Primary Current Rating
(Second ary Fusing Provided
Table 6B. (See reverse side)
Less than 2
动线:01
I Based on NEC 430. 73(C)
0111
2 or more
Table
Class cc fuse Protection Of Transformers With single-Winding Primaries
sEcondary fusing provided in accordance with Table 5C shown below
480 Volt Primary
See NEC Table 45031B)for exceptions
MECS and UL Maximum
Table 5c
Allowable Fusing (am ps)
I ittelfuise
With Only Primary Protection
Recommended fuse
Rated Secandary Maximum Rating of Fuse of Transformer
Current Amperes
Secondary Current Rating
Transformer
Primary
Currert
Control Power
Time Delay KLDR
Less than 9
Transformer
Transformer
g or more
1252
25
1/4
15/100
1/1C
50
0.10
1/2
10
3/1E
If 125% does not correspond to a standard fuse rating the next higher standard rating
3/10
3/10
may be used
0.21
6/10
4/C
27
8/10
1/2
0.42
1-1/4
5
0.73
31/2
500
10C0
15[0
3.13
200
2500
5
10
10
"These fuse ratings permissible only when secondary protect on is prcvided in accordance w th Table B
For Maximum Acceptable Rating of Primary Overcurrent Device
refer to table 2
For Maximum Acceptable Rating af Secondary Overcurrent Device
refer to table 5c
C 2010 Littelfuse POWR-GARD Products
ww. littelfuse com
Transformer Protection Basics
Expertise AppliedAnswers Delivered
Transformer Protection for Medium Voltage pad-mounted transtormers, and at other similar locations
Applications (above 600 Volts)
When properly applied, E-Rated fuses can protect against
high and low value fault currents. a supplemental device is
Introduction
needed in series to remove currents below the minimum
Medium voltage fuses are applied quite differently than
melting current rating of the fuse
fuses rated 600 volts and less. The biggest difference is that
Guidelines for E-Rated Fuses
medium voltage fuses are not intended to provide overload
protection. They should only be applied in situations where
Fuses with a rating of 100e or less will open(blow)
it will not be required to open small overcurrents Medium
within 300 seconds (5 minutes) at a current between
voltage fuses offer a much wider range of system voltages
200%and 240 of the"E"rating
thereby resulting in a correspondingly large number of fuse
Fuses with a rating above 100E will open(blow) within
voltage ratings
600 seconds(10 minutes) at a current between 220%
Descriptions and ratings of Littelfuse
and 264% ot the E rating
medium voltage fuses, along with
Fuse Sizing
some application data, are located in
the Medium Voltage Fuse section of
Fuses are sized at a percentage of the full load current
the Littelfuse POWR-GARD Catalog
Generally fuse size is based on 133 to 150 of
To download a copy visit
full load current
cswww.littelfuse.com/catalogs
Always round up to the next standard fuse rating
For questions, contact our Technical Support andE
As an example, .with a full load current of 104 amperes,
the fuse size based on 133 of full load current would be a
Engineering Services Group at 800-TEC-FUSE
138 ampere fuse. Such a fuse rating size does not exist, so
(800-832-3873 ). Definitions of terms used in this white
is permissible and recommended to round up to the next
paper can be found in the Technical application guide
standard size which in this instance is 150 amperes (150E)
section of the POWR-GARD Catalog. XX
e WWWBe sure to note that nuisance fuse openings can occur if
The following is a more detailed discussion of factors which
the fuse is sized too closely
nust be considered when properly selecting and applying
medium voltage fuses in electrical systems
Table 8
线
Suggested Minimum current limiting medium voltage fuse current ratings for
What are Medium Voltage Fuses?
self-cooled 2.4-15.5 kv power transformer applications
Littelfuse medium voltage fuses are silver-sand
48
7.2
non-expulsion design, current-limiting type devices
Fus
Max kV
When properly applied, they are designed to carry their
Trans-former Full
Fuse
nominal current rating continuously without" fatigue failure
kVA Rated
Current
Rating
This means that the fuse will not age, become brittle, or
Self-Coole
Amps(E)
,
Fuse
Fuse
Amos (ey Current
Amps(E)
deteriorate under the most severe duty cycling
Single Phasa Transformers
5715
5
304
When talking current-limiting medium voltage fuses, there
2.1
14
3
are two basic types: general purpose and back-up. genera
25
10.4
purpose fuses have the ability to interrupt both large and
2212056
52
3.5
1562
255050
580500
1133458
small short-circuits down to currents that would cause the
75
3134
1562
5.2
100
208
13.9
3.6
fuse to open within one hour. They are used to provide
104
348
50
174
short-circuit protection for transformers, switchgear, and
333
192006951046365231
8000
similar equipment
278
400
CO
9.6150
E83
173
250
1155
578
85
Back-up fuses are designed to protect only against high
60
868
fault currents, and must be used in series with equipment
Three Phase Transformers
that provides the circuit's required overload and low value
15
short-cIrcuit protection
6
24451.2
75
18
While"R-Rated"medium voltage(MV) fuses are specifically
125
524[
b80
10
5
136
15
4.5
designed to provide short-circuit protection for medium
27.2
18
15
voltage motor controllers and associated equipment,
77
100
36
35
18
E-Rated"MV fuses are considered to be general purpose
5
0540505
9012
10
301
45
fuses. Their mounting dimensions permit them to be
350
120
40.1
241
802
installed in a wide variety of medium voltage switches, in
2500
600
C 2010 Littelfuse POWR-GARDQ Products
ww. littelfuse com
Transformer Protection Basics
Expertise AppliedAnswers Delivered
直目目里目
Continuing with sizing of E-Rated fuses. the transformer
7. And where and whenever possible, fuses should
sizing guide in Table 8 shows the suggested minimum
protect the transformer against higher impedance
current limiting medium voltage fuse current ratings for
secondary faults
self-cooled 2. 4-15.5 kv power transformer applications
Transformer magnetizing or inrush current depends on
several tactors including the transtormer's design, the
amount of residual flux in the transformer core at the
Transformer protection
instant the transformer is energized, the point on the
A principle use of medium voltage fuses is to provide
voltage wave at which the switch is closed, and the
primary short-circuit protection for transformers
characteristics of the electrical system powering the
When selecting MV fuses to protect transtormers
transtormer. A power transtormers in-rush current
the following factors must be considered in descending
approximates 12 times the transformer full load current,
order of importance
While a distribution transformer s in-rush current can
exceed 25 to 40 times of the full load current. The
1. The fuse's voltage and interrupting ratings must equal
current generally lasts less than one-tenth of a second
or exceed system requirements at the point where the
fuses will be applied
Fiqure 2
Typical Example of Double-ended Loadcenter Operated with
2. The fuse's continuous current rating must be large
Normally Open Bus tie
enough to withstand transformer magnetizing (in-rush
current (Minimum Fuse rating)
3. The fuse's continuous current rating must be able to
withstand transformer overloading and emergency
业电器有限
rners
operation, while meeting all nEce requirements
like this
(Maximum Fuse Rating
4fusesromuthbreftectsesortmrcuitseontheleadsidewww.aphpo.com
of the fuses. Utility System Coordination
5. Fuses must coordinate with the transformer seconda
protection where and whenever possible ( Facility
010-5927
System Coordination)
6. Fuses must protect the transformer against secondary
bolted faults
Figure 1
Time-current Curves for Transformer Protection Application
To determine the minimum size fuse that will withstand
1000
the in-rush current it is recommended that the in-rush
current be obtained from the transformer manufacturer
400
Typical transformer
damage curve for
Then, note the current on the fuse s minimum melting
200
3-pha
time-current curves at o10 second. this is illustrated in
anc single-phase faults
more detail in Figure 1. The fuse whose minimum melting
on 1-phase transformers
curve is just to the right and above the transformer inrush
point becomes the minimum fuse rating to use for properly
Melting Curve
protecting the system
Medium voltage fuses with current ratings that equal
exceed a transformer s self-cooled. full load current will
Fuse maximum
Clearing Curve
usually meet such a requirement when the in-rush current
Maximum
does not exceed 12 times transformer full load current
Transformer
Overload
However, transformers are generally operated at close to full
cUrrent
oad current on a continuous basis and are often overloaded
under emergency conditions. a typical example is a double-
ended loadcenter operated with a normally open bus tie
See Figure 2
”°°R月883月罰导冒
CURRENT IN AMPERES
C 2010 Littelfuse POWR-GARDQ Products
ww. littelfuse com
Transformer Protection Basics
Expertise AppliedAnswers Delivered
直目目里目
Each transformer is rated to carry 150%of the load on
its half of the loadcenter With loss of service to one
transformer, the main switch for that line is opened and
the bus tie switch is closed. this shifts all load to the
remaining transformer. The system is operated in an
overloaded state until the other line is back in service
the outage continues for a long period of time, manual load
shedding can be used to control transformer overloading
Other similar operating schemes also result in transtormer
overloading. As a result, medium voltage fuses usually have
continuous current ratings larger than required to withstand
transformer in-rush current
NECQ Article 450 covers transformer installations an
establishes the maximum ratings of transformer overcurrent
protective devices. Regarding medium voltage fuses, NEC
Article 450.3 states, in part
Overcurrent Protection of transformers shall comply with
NEC Article 450.3(A)-Transformers Over 600 Volts
Nominal, and shall be provided in accordance with Table 9.
NOTE/n this section. the word"transformer shall
a业电器有限公司
mean a transformer or polyphase bank of two or more
single-phase transformers operating as a single unit
Table 9
公司网址:ww.pepo.com
Based on NEC Table 450.3(A)Maximum Rating or Setting of Overcurrent Protection for Transformers Over 600 Volts
(as a Percentage of Transformer-Rated current
销售热 Primary Protection Over9/90
Secondary Protection(See Note 2)
Over 600 volts
600 Volts or less
Location limitations
Transformer rated
Circuit Breaker
Circuit Breaker
Impedance
(see Note 4)
Fuse Rating
see note 4
Fuse Rating
Circuit Breaker or
Fuse Rating
Not more than 6%(see Note 1)
600%
300%
300
250
125%
Any location
More than 6% but not more than
10%(see Note 1)
400%
300%
250%
225%
125%
any (see Note 1)
250%
Not Required
Supervised
Not more than 6%(see Note 5 for
300
25
Locations Only /see
Secondary protection
6U0%
250%
Note 3
More than 6% but not more than
10%(see Note 5 for Secondary
400%
300%
250%
225%
Protectio
Note 1-I the required fuse rating or breaker setting does not correspond to standard rating/settings, the next higher rating/setting may be used.
Note 2-If secondary overcurrent protection is reguired, no more than six breakers or sets of fuses may be grouped in any one location. When multiple overcurrent devices are
usei, the sun ofall device ratings shall not exceed the allowed value of any sinigle device. ir bolh breakers and /uses are used, the lola o/ device ratings shall noi
exceed that if using only fuses
Note 3-A supervised location" is one where maintenance and supervision conditions ensure that only qualified persons are allowed to monitor and perform installation service
on the transformer
Note 4- Electronically actuated Tuses set to open at a specific current shall be set and calibrated in accordance with the corresponding settings of the circuit breakers involved.
Note 5- Separate secondary protection is not necessary if the transformer is equipped with a coordinated thermal overload protection provided by the manufacturer.
Additional technical information and application data for Littelfuse POWR-GARD protection relays, fuses and other circuit prote ction and safety products
canbefoundonwww.littelfuse.com.ForquestionscontactourTechnicalSupportGroup(800-832-3873).Definitionsoftermsusedinthiswhitepapercan
befoundintheTechnicalApplicationGuidesectionofthepOwr-gardCatalog.Todownloadacopyvisitwww.littelfuse.com/catalogs
Form No. pf753
C 2010 Littelfuse POWR-GARDQ Products
ww. littelfuse com