Product overview
Introduction
The documentation in this manual is intended
to provide you with comprehensive
intormation on how to set up your Modbus
Plus Option card for communication over a
Modbus plus communication link
About this
This manual is intended to be used both as communication system. The list of contents is
manua
an instructional and a reference manual. It
also a decision route that will guide you
only brietly touches on the basics of the
through the decisions you have to make
Modbus Plus protocol whenever it is
before you set up your system
necessary for gaining an understanding of the
Modbus plus option Card for the danfoss
Even if you are an experienced Modbus Plus
VLT 5000 Series
programmer, we suggest that you read this
manual in its entirety before you start
This manual is also intended to serve as a programming, since important information
guideline when you specify and optimize your can be found in all sections
Assumptions
This manual assumes that you are using a application. Also all requirements stipulated in
Modbus Plus option Card in conjunction with the Modbus Plus standard as well as well as
a danfoss vlt 5000 Series Drive. It is alsc
those pertaining to the VLt Variable Speed
assuming that you as a master, are using a
Drive, are strictly observed as well as all
PLC or Pc that is equipped with a serial
mutations therein fully respected
communication card supporting all the
Modbus plus communication services
required by your
What you should The Danfoss Modbus Plus Option Card is
therefore assumed that you have ful
already know
designed to communicate with any master knowledge of the PC or PLC you intend to
abiding by the Modbus Plus standard. It is
use as a master in your system
VLT 5000 Series Modbus Plus option Card
Agency Approval The Modbus Plus Option Card is UL listed
and cUL approved
The Modbus Plus Option card is Ce pending
consult factory
Danfoss is a modconnect partner
Modbus plus
Style Enclosure
VLT 5000
Modbus Order No. Modbus Order No
Part numbers
Description
with memory card
ithout memory card
Bookstyle
5001-5006,200-240V176F1550
176F1558
5001-5011,380-500V
Compact Chassis5001-5027,200-240∨176F1551
176F1559
5001-5052,380-500V
Compact NEMA1250015027,200-240176F1550
176F1558
5001-5052,380-500V
Compact Chassis5032-5052,200-240V176F1551
176F1559
5060-5250,380-500
Compact NEMA125032-5052,200-240176F1551
176F1559
5060-5250,380-500V
Additional
175R5285-Option Card Installation
GM-MBL-001 RevD- MODICoN Modbus
Reference
Instructions
Plus Network Planning and Installation guide
Literature
175R5271-VLT 5000 Series Adjustable
Frequency Drive Instruction
Appropriate Modicon Programmable
Manual
Controller Systems"manual for your
equipment.
Contact Danfoss for these manuals.
(Contact MODICON for these manuals.
4
a
VLT 5000 Series Modbus Plus Option Card
Installlation
The following installation section is specitic to the Modbus Plus option card. For more specific
intormation on installation and operation of the VLt 5000 refer to the VLT 5000 Series
Adjustable Frequency Drive Instruction Manual 175R5271
WARNING:
The VLT Adjustable Frequency Drive contains dangerous
voltages when connected to line voltage. After disconnecting
from the line wait at least 15 minutes before touching any
electrical components. Only a competent electrician should
carry out the electrical installation. Improper installation of the
motor or the vLT may cause equipment failure, serious injury or
death follow this manual and national electrical codes and
local safety codes
WARNING
Electrostatic Precaution; Electrostatic discharge(ESD). Many
electronic components are sensitive to static electricity. Voltages
so low that they cannot be felt, seen or heard, can reduce the
life, affect performance, or completely destroy sensitive
electronic components.
When performing service, proper ESD equipment should be
used to prevent possible damage from occurring
CAUTION
It is the responsibility of the user or the person installing the VLT
to provide proper grounding, as well as motor overload and
branch circuit protection according to the National Electrical
Code and local codes
VLT 5000 Series Modbus Plus option Card
Installation for
Bookstyle Units
1. Access to Control To remove the Local Control Panel (LCP)
A
Card cassette
pull at the top of display(a)
To remove the protective cover gently pry at
the notch(B
2. Removing
Remove any control wiring by unplugging
Cassette
the terminals and removing the ground
Unscrew the two captive screws (A)
securing the cassette to the Chassis
Lift at the bottom of the cassette( B) and
unhinge at the top
(A)
①-K)②
(B)
a
VLT 5000 Series Modbus Plus Option Card
3. Removing Ribbon Unplug the two ribbon cables(A) and(B
Cables
from the control
NOTE: The ribbon cables will need to be
replaced on the same connections from
which they were removed
(A)
4. Removing LCP
Carefully push in at the right side corners of
we Press
cradle
the LCP cradle to release clips, and gently
pull out to release clips at left side
Lift
Press
(A)
5. Ribbon cable
Be sure that the exposed wire portion of the
Installation on
ribbon cable(A) is facing the front of the
Option Cards
socket (B)
Pull up the collar(C)of the ribbon cable
socket, insert the cable and push the collar
(c)
closed
Repeat for all ribbon cables.
TTmInTnmm
山
Memory card
K(
Control car
VLT 5000 Series Modbus Plus option Card
6. Modbus plus
NOTE: Address switch settings need to be
Address Switch
made prior to option card installation Reter to
Understanding Module Address Switches
section in this manual
Address
Switches
7. Ribbon cable
Carefully route cables through the opening
Routeing
in the back of cassette(A)
(A)
8. Securing Option
Slide the edge of the option card into the
Card
slot in the side of the cassette ( A
Secure the other edge of the option card
with the self-tapping screws provided (B
torque the screws to7.1 LB. IN
a
VLT 5000 Series Modbus Plus Option Card
9. Ribbon cable
Be sure not to twist cables
installation on
Insert cables in corresponding sockets
Control card
上口
■■■■■■■■■■■
10. Ribbon cable
Be sure that the exposed wire portion o
(A)
installation on
the ribbon cable (A)is facing the front of the
Control card
socket(B
Pull up the collar(C)of the ribbon cable
l山
socket, insert the cable and push the collar
Repeat for all ribbon cable
B
11. Replace the LCP Insert the right side clips first
Cradle
Push down on the right side to snap into
place.
VLT 5000 Series Modbus Plus option Card
12. Replacing the
Re-connect the ribbon cables a and B
Cassette
NOTE: The ribbon cables will need to be
on the same
which they were removed
B
(A)
13. Replacing the
Hinge the control card cassette at the top
of the drive(a)ar
hten the two s
(B)to7.9LB·N
Replace the LCP, control signal wiring
protective cover.
恐
14. Network
Network connector installs through the top
Connector
of the control card cassette
Remove connector access knock-out(A)in
top cover of drive
15. Wiring Bracket
ing bracket b)to the top of the
(B)
drive and torque screws to 10.6 LB
NOTE: Cable clamps are to be placed over
the wire insulation for strain relief only. DO
NoT ground the cable shield