General
△
CAUTION
Before Handling the actuator,
please read instruction manual
and be well aware how toto do
NA Series actuator is a engineered products which has been designed for
usage of automation of 90 rotary valve or same operating principle
equipment. Internal provisions like as self-locking which prevent reverse
action from valve, Manual Override, and mechanical torque
switches(except for NAO6&09)which protect actuator from overload
Space heater for anti-condensation provide optimum condition for actuator
operation
Enclosure
Al alloy enclosure is treated by Hard-anodized and powder coated
Therefore it can be used under severe corrosive atmosphere
All enclosures are designed to provide iP67grade ingress protection with
explosion proof structure and to provide best performance under any
circumstances
Performance and applicable range
13 model of na06.09.15.19.28.38.50.60.80.100.150.200.250
provide various torque 6Kg. m- 250Kg. m and these are suitable for
operation of 50A-600A of butterfly valve, 40A-400A of Ball valve, and
other g0 rotary equipment like as Damper
OONOAH
General
Lubrication and convenient installation for any direction
NA Series actuator has double worm gearing and the mechanism is fully
filled with grease
There is no leak of lubricant because housing is totally enclosed structure
Therefore installation for any direction is possible on the purpose
Inspection, Measurement and test
The performance and quality of NA Series actuators are certified by
factory through out the leak, torque test and other necessary
measurement after assembly and 100% certified product only delivered to
customer
Temperature, Humidity and Altitude
NA Series actuators are designed suitable for following condition
User should note these conditions when you select actuator
Ambient Temperature
-10°C-55C
Max. Temp. of fluid
80°C
Relative humidity
:RH90%
Altitude
Lower than 1000m
OONOAH
Commissioning
1. Please check if the supplied actuator is suitable one for your
application
2. Please check Model, Mounting base, Electrical specification and
options comparing to your specification for puschasing
(Can check these on the name plate mounted on actuator)
For your information, EMIcO recommend Na series actuator for your
Butterfly /Ball valve as follows.
Model
Butterfly Valve Ball valve(2-way) Ball valve(3-way)
NAo6
80A
40A
NA09
100A
50A
40A
NA15
125A
65A
50A
NA19
150A
80A
65A
NA28
200A
100A
80A
NA38
250A
100A
NA50
125A
NA60
300A
150A
125A
NA80
350A
150A
NA100
200A
NA150
4004450A
NA200
500A
250A
200A
NA250
600A
300A
250A
o Above table shows suitable size of actuator for valves which work under
10Kg/Cm of operating pressure
If you need more information, please consult with factory or regional
representative
3. Because Electric wiring diagram, test report and instruction manual are
supplied together with actuator, please check if these are supplied or
not
4. Please check tool and screw set for installation
△
Caution
1. When you handle actuator which is not completely installed, please
make sure that power should not be supplied into the actuator
OONOAH
Commissioning
2. If limit switches are not set yet, please make sure that actuator should
not be fully open or close
Actuator should be stored at dry and clean place if it is not immediately
installed after delivery
The place should
There should be no severe vibration and temperature change in the place.
If it is high humidity, power should be supplied at least every two week in
order to operate the heater to prevent condensation
Also, please do not remove the plug which mounted into actuator cable
entry until wiring is ready in the field
E CAUtIon
△
If trouble due to inappropriate storage
and place, EMICO can not guaranty the
performance and quality
OONOAH
Commissioning
Please be careful not to operate actuator to fully close or fully open until
the direction of actuator is not confirmed(Especially 3 phase electricity)
Also if limit switches are not completely set yet, it can be a major cause of
damage of valve and actuator
(Limit switches are already set when delivery, limit switches can be set
again in the field if necessary)
It is very simple to operate actuator by manual or electrical as follows
Manual operation
If you want to operate actuator by manual, pull the lever ( toward
handwheel), so that clutch is to be engaged with handwheel
If it is engaged, then you can operate actuator to any direction by manual
Direction Indication of Open and Close is marked on the handwheel and
handle cover and in general, to turn clockwise is close and counter
clockwise is open
Electrical operation
After completion of wiring, you can operate actuator by switch in the
Local panel
If electricity is supplied, actuator automatically returns from manual to
electrical operation mod
If lever lean toward opposite side of handwheel, you can acknowledge it
as electrical operating mode
OONOAH
Indication
The Indication of valve position is done by indicator which is shown
through the window of actuator top cover
CLOSE
CLOSE
卫mz
Tm
彐s15
Open
Close
Indicator is designed same as shape of disc of butterfly valve and user
can easily acknowledge the valve position from a distance
OONOAH
Electrical wiring
Taking off Top cover
By using the L-wrench, unscrew the screw of top cover and take off the
top cover from assembly
Electrical wiring
Wiring should be done as per the wiring diagram which is provided
together with actuator. Especially electricity (voltage, phase and hertz
should be confirmed comparing to the details on nameplate
△
Eh Warning
Relays for power supply should not be
connected to more than two actuators
Grounding, Heater and internal wiring
1. Grounding lug in actuator and outside of actuator should done
Connect the grounding wire to the position of the following mark
2. Wiring to heater should be done
3. Please make sure that wiring to terminal block should be tightly done
4. When wiring to terminal block, there should be some gap between the
wires in order to prevent electric shortage due to the interference
between the wires
3Phase(220V, 380V or 440V or others)electric power
Danger
△
NEVER connect phase conductors( L1, L2, L3)or
neutral conductor(N) to the protective earth
terminal marked pe
OONOAH
Electrical wiring
Because there is no way to identify each phase among 3 phase,user
should confirm the actuator correct rotating direction
Otherwise, it can be a major problem of motor burning
In order to check correct rotating direction for start up, followings should
be done
Make valve disc 45 position by using manual handwheel of actuator
2. Push the Close or Open switch for approx. 3seconds, check the
rotating direction of valve disc
3. f direction of valve disc is reverse, immediately stop the actuator and
check the wiring again
Then change 2 wires each other among 3 wires(UVW)
Single phase (110v or 220V)Power
When wiring, please be careful not to supply power to open and close
terminal simultaneously.
This is a major cause of motor burning and after service at free of charge
is impossible
A
caution
Without confirmation rotating direction of 3 phase, actuator ca be
operated in reverse direction.
In this case, limit switches can not function and therefore Jamming of
gearing or motor burning can occur.
This is not a trouble which free after service is applicable.
others after wiring
After completion of wiring, make internal wires well arranged by using
cable tie etc and remove substance in the actuator if any in order to
avoid any trouble due to the substance
After completion of all wiring and arrangement in internal, put the top
cover on the housing and fasten the 4 retaining screws