文件名称:
POINT I/O Input Modules.pdf
开发工具:
文件大小: 573kb
下载次数: 0
上传时间: 2019-10-12
详细说明:POINT I/O Input Modulespdf,POINT I/O Input ModulesPOINT /0 Input Modules 3
ATTENTION Environment and Enclosure
△
This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications
as defined in IEC publication (06G4-1), at altitudes up to 2000
d
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR Publication 11. Without
appropriate precautions, there may be potential difficulties
ensuring electromagnetic compatibility in other environments
due to conducted as well as radiated disturbance
This equipment is supplied as"open type"equipment. It must
be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and
ppropriately designed to prevent personal injury resulting from
le only by the use of a tool Subsequ
oublication may contain additional information regarding
specific enclosure type ratings that are required to comply with
certain product safety certifications
See NEMA Standards publication 250 and IEC publicatie
60529, as applicable, for explanations of the degrees of
protcction provided by different types of enclosure. Also, sce the
ppropriate sections in this publication, as well as the
Allen-Bradley publication 1770-4.1(Industrial Automation
Wiring and Grounding Guidelines), for additional installation
requirements pertaining to this equipment.
ATTENTION
POINT I/O is grounded through the DIn rail to chassis
ground. Use zinc plated, yellow chromated steel DiN rail to
△
assure proper grounding. Using other DiN rail materials(e.g
aluminum, plastic, etc. which can corrode, oxidize or are poor
conductors can result in improper or intermittent platform
Publication 1734-IN051F-EN-E- August 2005
4 POINT /0 Input modules
WARNING EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous
Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate to
this equipment by using screws, sliding latches,threaded
connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I,
If this product contains batteries, they must only be changed
in an area known to be nonhazardous
ATTENTION
Preventing Electrostatic Discharge
△
equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved
Do not touch connectors or pins on component boards
Do not touch circuit components inside the equipment
tf available use a static-safe workstation
When not in use, store the equipment in appropriate
Before You Begin
This Series C POinT I/O product can be used with Device Net and
PROFIBUS adapters. It can be used with ControINet and Ethernet adapters
using rslogix 5000 software, version 1 1 or higher
Read this manual for information about how to install this 1734 POINT I/O
Module
Publication 1734-IN051F-EN-E- August 2005
POINT /0 Input Modules 5
Identify the Components
Csc the figurc to identify the cxtcrnal fcaturcs of the modul
Locking
Mechanism
Insertable 1/0
Module
Diagram
FTB Removal
eying, DIN Rail
Handle
Removal terminal
Block(RTE
Interlocking
M3u
About the module
The 1734 sink input modules are available in 2 input, 4 input, and 8 input
They install in mounting bases that mount on a din rail. All wiring is made to
a removable terminal block mounted on the mounting base.
Install the Mounting base
To install thc mounting basc on the din rail, proceed as follows
1. Position the mounting base vertically above the installed units
adapter, power supply, or existing Imodule)
Publication 1734-IN051F-EN-E- August 2005
6 POINT /0 Input modules
2. Slide the mounting base down allowing the interlocking side pieces to
engage the adjacent module or adapter
3. Press firmly to seat the mounting base on the din rail
The mounting base will snap into place
4. To renove the mounting base fromm the din rail, remove the module,
and use a small bladed screwdriver to rotate the base locking screw to
a vertical position
I his releases the locking mechanism
5. Lift straight up to remove
Install the l 0 Module
The module can be installed before or after base installation. Make sure that
the mounting base is correctly keyed before installing the module into the
mounting base. In addition, make sure the mounting base locking screw is
positioned horizontal referenced to the base
ARNING
When you insert or remove the module while
backplane power is on, an electrical arc can occur. This
could cause an explosion in hazardous location
installations
Be sure that power is removed or the area is
nonhazardous before proceeding. Repeated electrical
arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may
create electrical resistance that can affect module
operation.
1. Using a bladed screwdriver, rotate the keyswitch(2) on the mounting
d for th
le type
nle b
installed aligns with the notch in the base.
2. Make certain the din rail locking screw is in the horizontal position
You cannot insert the module if the locking mechanism is unlocked
Publication 1734-IN051F-EN-E- August 2005
POINT /0 Input Modules 7
3. Insert the module straight down into the mounting base and press to
secure
Install the Removable Terminal Block(RTB)
A removable terminal block is supplied with your wiring base assembly. To
rernove, pull up on the RTB handle. This allows the mounting base to be
removed and replaced as necessary without removing any of the wiring. To
reinsert the removable terminal block, proceed as follows
1. Insert the end opposite the handle into the base unit
This end has a curved section that engages with the wiring base
2. Rotate the terminal block into the wiring base until it locks itself in
3. If an I/O module is installed, snap the rtb handle into place on the
mo
WARNING
When you connect or disconnect the removable tcrmina
block (rtb) with field side power applied, an electrical arc
△
can occur.This could cause an explosion in hazardous
location installations. Be sure that power is removed or the
area is nonhazardous before proceeding
Remove a Mounting Base
To remove a mounting base, you must remove any installed module, and the
module installed in the base to the right remove the removable terminal
block(if wired
1. Unlatch the RtB handle on the l/O module
Publication 1734-IN051F-EN-E- August 2005
8 POINT /0 Input modules
2. Pull on the rtb handle to remove the removable terminal block
WARNING When you connect or disconnect the removable terminal
block(rib)with field side power applied, an electrical arc
△
can occur. This could cause an explosion in hazardous
location installations
Be sure that power is removed or the area is nonhazardous
before proceeding
3. Press on the module lock on the top of the module
4. Pull on the l o module to remove from the base
WARNING
When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations
Be sure that power is removed or the area is nonhazardous
before proceeding. Repeated electrical arcing causes
excessive wear to contacts on both the module and its
mating connector. Worn contacts may create electrical
resistance that can affect Imodule operation
5. Repeat steps 1, 2, 3, and 4 for the nodule to the right
6. Use a sImall bladed screwdriver to rotate the orange base locking
screw to a vertical position
This releases the locking mechanism
7. Lift straight up to remove
Publication 1734-IN051F-EN-E- August 2005
POINT /0 Input Modules 9
Communicate with your module
1/O) messages are sent to(consumed and received from (produced) the
POINT I/O modules. These messages are mapped into the processors
memory. This POINT I/O input module produces 1 byte of input data
(scanner Rx). It does not consume I/o data(scanner Tx)
Default Data Map for the 1734-1B2 Input Module
Message size: 1 Bvte
765432
Produces(Rx
Consumes (Tx)
No consumed data
Where: 0=channel 0, 1=channel 1: 0= off. 1=on
Default Data Map for the 1734-1B4 Input Module
1 Bvte
2
Produces(Rx)
Consumes (Tx)
No consumed data
Where: 10-channel0 11-channel 1. 2-channel 2 and 3-channel 3: 0-off 1-on
Default Data Map for the 1734-IB8 Input module
1 B
2
Produces(Rx
61514|13
Consumes(Ix)
No consumed data
Where: 0=channel 0. 1= channe 1, 2= channel 2 and 3=channel 3: 4=channel 4
15=channel 5, 16=channel 5, 17 equals channel 7: 0=off, 1=on
Publication 1734-IN051F-EN-E- August 2005
10 POINT 1/0 Input modules
Wire the Input Modules
1734-B2
1734-B4
1734-B8
dule status
Satun Nework Status
Status of input 0
Status- Input 0&4
Status of Input 1
Status-Input 1 &5
Status of Input 2
Status-Input 2&6
Status of Input
lalus-Inpul 3&7
nput O
nout 1
Input O
Input 1
Input O
Input 1
Input 3
put
Input 3
四
C
Input 4
Input 5
OoI Inpu
Input-0 and
Input=0, 1, 2 and 3
Input-0.1,2.3.4.5,6ad7
NC= No Connection (2 and 3)
on(4 and 5) Note: V and C are daisychained
C=Common(4 and 5)
from either the adapter
1734-FPD. 1734-EP24DC or from
a user-supplied auxiliary terminal
WARNING
When you connect or disconnect wiring while field side
power is on, an electrical arc can occur. This could cause an
ll:
Be sure that power is removed or the area is nonhazardous
before proceedin
Publication 1734-IN051F-EN-E- August 2005
(系统自动生成,下载前可以参看下载内容)
下载文件列表
相关说明
- 本站资源为会员上传分享交流与学习,如有侵犯您的权益,请联系我们删除.
- 本站是交换下载平台,提供交流渠道,下载内容来自于网络,除下载问题外,其它问题请自行百度。
- 本站已设置防盗链,请勿用迅雷、QQ旋风等多线程下载软件下载资源,下载后用WinRAR最新版进行解压.
- 如果您发现内容无法下载,请稍后再次尝试;或者到消费记录里找到下载记录反馈给我们.
- 下载后发现下载的内容跟说明不相乎,请到消费记录里找到下载记录反馈给我们,经确认后退回积分.
- 如下载前有疑问,可以通过点击"提供者"的名字,查看对方的联系方式,联系对方咨询.