■ Performance
Current indication accuracy +3 A (for Models with heater burnout detection)
Insulation resistance
100 MQ2 min(at 500 VDC)between primary and secondary
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between primary and secondary
Vibration resistance
Vibration frequency: 10 to 55 Hz, acceleration: 50 m/s2 in X, Y, and Z directio
Shock resistance
300 m/s three times each in six directions along three axes
Weight
prox. 200 g(including terminal cover
Degree of protection
P20
Memory protection
EEPROM(non-volatile memory)(num ber of writes: 100,000)
Installation environ ment
Overvoltage category Il, pollution degree 2(according to IEC 60664-1)
Approved standards
UL508 Listing), CSA222 No. 14
EN50178
EN61000-6-4(EN55011:1998,A1:1999 Class A, Group1)
EN61000-6-2:2001
Communications Specifications
Transmission line connections
Multipoint
Communications method
RS-485
Max transmission distance 500 m
No, of nodes
31(via multidrop connections)
Synchronization method
Stop-start synchronization
Communications baud rate
9.6, 19.2, 38.4 or 57.6 kbps, Default: 9.6 kbps
Transmission code
ASCII
Communications data length
7 or 8 bits Default: 7
Communications stop bits
1or 2 bits Default: 2
Communications parity
Vertical parity: None, even, or odd, Default: Even
Flow control
None
Current Transformer Specifications (Order Separately)
Item
Specification
Model number
E54-CT1
E54-CT3
Max continuous heater current 50 A
120 A(See note.
Dielectric strength
1.000 VAC for 1 min
Vibration resistance
98m/s2,50Hz
Weight
Approx. 11.5 g
Approx 50 g
Accessories
None
Connection terminals(2)
Plugs(2)
Note The maximum continuous current of the g3za is 50 a
Optimum Cycle Control
Optimum cycle control is performed by driving SSRs according to
load power detection and trigger signals (Zero-cross SSRs are
used
Noise is suppressed while ensure high-speed response by turning
outputs ON and OF F each half cycle to achieve high-precision
temperature control
Manipulated/\
variable: 20%c
Multi-channel Power Controller G3ZA
OmROn
Connections
Terminal Arrangement
Models with 8 Channels(Control Points),
Models with 4 Channels(Control Points)
No CT Inputs, and No Heater Burnout Detection
CT Inputs, and Heater Burnout Detection
2 VCC. 21 mA
12vDC,21
+r12 VDC
C-5 CH6 COM
CH1
12vDC,2mA一-
luoc
C. 21 mA
Trigger output
⊕⊕⊕⊕⊕
Fr12 yD
CH2
COM CH3
CH4
COM
⊕⊕⊕⊕
CH2 COM CH3 H4 COM
24
READY
D
rm output connector( See note 2)K
Alar outout
oltage of 400 to 480 V)
Models with Load Power Supply Voltage ERROR
Models with load power
of 100 to 240 V
of 400 to 480 V
⊕⑤○⊕○
⑨⊕○⑨○⊕
B{+)Rs485A(-)
B(+)Rs435A(-
Power supply voltage
Load power supply voltage
supply volley
0o tc 210 V
240 VAC
uad wuweI supply volayu
506H
Note: Connect the power supply(100 to 240 VAC)for the
Note: Connect the power supply(100 to 240 VAC) for the
G3ZA across terminals 1 and 2 and the load power
G3ZA across terminals 1 and 2 and the load power
supply for the SSR loads across terminals 4 and 6
supply for the SSR loads across terminals 4 and 6
Note: 1. Applicable CTS: E54-CT1 and E54-CT3
2. Use C-Grid SL connectors from molex inc
C-Grid SL Housing
Mode|:51030-6303
C-Grid SL Housing(press-fit
Mode:52109-0660
operation Indicators
Communications Unit Number
Operation in
ndicator
Meanin
Set a communications unit number on SW1 so that the host system
READY (Greer
Lit while power is being supplied.
can identify the Controller
SD/RD (Orange)
Lit while communicating with the host
0123456789AB
Occ
Lit while a control output is ON.
Unit No.0001c2|03040506070809101
ERROR(Red)
Lights or flashes when an error is detected
Setting Switches
Note: a unique unit number must be set for each node(Controller)on
the same communications line do not set the same unit
Always turn OfF the power supply before setting the switches. The
number for more than one node
witch settings are read only when the power supply is turned oN
Use a flat -blade screwdriver to set the switches and be sure not to
Communications Baud rate
leave a switch set between two settings
Set the baud rate for communicating with the host system on SW2
0
Baud rate
38.4
Do not set
SW1
SW2
Default
Multi-channel Power Controller G3ZA
omRon
Connection Configuration
rigger sig
H
Note: Connect a power supply with the same phase as the SSRs to
the load power supply terminals on the gaza
Dimensions
Note: all units are in millimeters unless otherwise indicated
Multi-channel Power controllers
G3ZA-4H203-FLK-UTU
G3ZA-4H403-FLK-UTU
G3ZA-8A203-FLK-UTU
G3ZA-8A403-FLK-UTU
Mounting hole dimension
4.6 ds
⊕⊕⊕⊕⊕
76 max
84x3
⊕⊕⊕O⊕○
H4.5
Oe○6/
Multi-channel Power Controller G3ZA
omRon
Accessories (Order Separately
Current Transformer(CT)
E54-CT
中
Current Transformer (CT)
E54-CT3
E54-CT3 Accessories
ugs
DIN Track
End Plate(Stopper)
-0.2
PFP-100M
PFP-M
M4 x8
PFP-50N
screw\\
P
35±03
4
are for the pfp50N
Multi-channel Power Controller G3ZA
omRon
Precautions
△ WARNING
Precautions for safe Use
Do not touch the terminals and the wires while power is
Do not use the product in the following locations
being supplied. Doing so may possibly result in electric
△
Locations subject to direct radiant heat from heating equipment
shock make sure that the terminal cover is installed
Locations where the product may come into contact with water
before using the product
or ol
Locations subject to direct sunlight
△ CAUTION
Locations where dust or corrosive gases(in particular, sulfuric
or ammonia gas) are present
Do not allow pieces of metal, wire clippings, or fine
metallic chips or filings from installation to enter the
Locations subject to extreme temperature changes
product. Doing so may occasionally result in electric
Locations where icing or condensation may occur
shock fire, or malfunction
Locations subject to excessive shocks or vibl
Do not use the product in locations of flammable or
explosive gases. Doing so may occasionally result in
2. Use this product within the rated load and power supply
minor or moderate explosion, causing minor or moderate
3. Ensure that the rated voltage is achieved no longer than 2 s after
injury, or property damage
turning the power On
4. Use/store within the rated temperature and humidity ranges
Do not attempt to disassemble, repair, or modify the
product. Doing so may occasionally result in minor or
5. Minimum mounting distance of G3ZA is 10 mm
moderate injury due to electric shock
When mounting the G3ZA near the SSRs, mount the G3Za so as
to not interfere with the heat dissipation of the SSR
Perform correct setting of the product according to the
6. Use the specified size of insulated-type crimp terminals( M3,
application. Failure to do so may occasionally cause
width: 5.8 mm max. )for wiring and attach insulative sleeves. TO
unexpected operation, resulting in minor or moderate
connect bare wires, use AWG22(cross section: 0.326 mm2)to
injury, or damage to the equipment
AWG14(cross section: 2.081 mm2)to wire the power supply
Ensure safety in the event of product failure by taking
terminals and AwG22 (cross section 0.326 mm?)to AWG16
safety measures, such as installing a separate monitoring
(cross section: 1.039 mm)for other terminals
system to provide alarms for preventing excessive
7. Be sure to confirm the correct terminal and polarity when wiring
temperature rise. Product failure may occasionall
the terminal block and connectors
prevent control operation, resulting in damage to the
connected facilities and equipment
8. Do not connect any conductors to unused terminals
9. In order to prevent inductive noise, wire the lines connected to the
Tighten the terminal screws securely using a tightening
product separately from power lines carrying high voltages or
torque within the following ranges. Loose screws may
currents. Da not wire in parallel with or in the same cable as
occas ionally cause fire, resulting in minor or moderate
injury, or damage to the equipment
power lines. Other measures for reducing noise include running
lines along separate ducts and using shield lines
Terminal screws: 0. 40 to 0.56 N.m
10. Attach a surge suppressor or noise filter to peripheral devices that
generate noise(in particular, motors, transformers, solenoids
magnetic coils, or other devices that have an inductance
component)
Do not install the product near devices generating strong high
frequency fields or surges. When using a noise filter. check the
voltage and current and install it as close to the product as
1. For a safety disconnection of the power-line in the application, the
quipment must be provided with disconnecting devices suitable
for isolation
e.g., circuit breakers defined in lEC60947-2, power switches
defined in IEC60947-3, power plugs, etc.
12. The G3zA is for single-phase loads only. Connect only single
hase zero-cross SSRs
Do not connect three-phase SSRs, magnetic relays, or SSRs that
do not have a zero-cross function
Multi-channel Power Controller G3ZA
OmRon
Precautions for correct use
Mounting End Plates
Be sure to mount an end plate on each side of the g3za so that i
Wiring
does not slide on the din track
Use M3 crimp terminals.
To mount an end plate hook the bottom of the end plate on the
bottom of the dIN Track(1), place the top of the End plate on the din
Track(2), and then pull down on the End Plate. Tighten the screw on
5.8 mm max
the end plate to secure it
e
Use wires that withstand a minimum of 70 c
DIN Track
Secure the din track with screws in at least three locations
我O⊕○
⑧○BOa
DIN Track: PFP-50N(50 cm)/PFP-100N (100 cm)
End plate
End plate
Note: Always mount one End Plate on each side of the G3zA
nstallation Example
When installing the SSRs next to the G3zA, provide sufficient space
between the G3ZA and SSRs, as shown in the following diagram
Reference example
When applying 10 A to the G3PA-210B-vVD (a manipulated variable
of 100%), separate the SsRs from the G3Za by at least 20 mm
Mounting the G3ZA
Do not touch the G3ZA while power is being supplied
Mount the G3ZA as shown in the diagram. First, pull down the dIN
Track mounting hook(1)and hook the top of the G3ZA on the DIN
G3ZA
Track(2). Then press the G3za onto the DIN Track far enough so
that it can be locked in place (3 )and push the DIN Track mounting
hook up to lock the G3Za in place (4)
⊕○⊕O⊕
Mounting with Screws
Removing the G3zA
Mounting Dimensions(Unit: mm)
Two 4.2 dia
Use a flat-blade screwdriver to pull down the dIN Track mounting
hook (1)and then pull out on the bottom of the G3ZA(2)
↓
(1)
Multi-channel Power Controller G3ZA
omRon
Multi-channel Power Controller G3ZA
OmROn
Multi-channel Power Controller G3ZA