2. Operation
Before you can start operating the SAMSON Positioner, you have to load the samson ap
plication program which can be ordered via the HArT Communication Foundation(HCF)
When using the[e]key to go from the online menu down to the submenu
you can view the list containing all the application programs presently stored
in the communicator
2.1 Start-Up
Supply the positioner with pneumatic power (air supply) and connect to the reference varia
ble >4 mA
2.1. 1 Zero adjustment
mportant:
If zero has not already been adjusted upon positioner mounting as described in the moun
ting and Operating Instructions EB 8380-1EN, chap. 4.1, mechanical zero adjustment must
be carried out with the valve being in closed position prior to initialization of the device
1. Push the zero lever(marked by an arrow and O symbol on the cover plate
direction indicated by the arrow as far as it will go
For control valves with the position OPEN, i. e actuators with"Actuator stem retracts"
you must cover the bore on the cover plate marked by a hand symbol with your Finger
so that the valve moves in closing position
2. Establish the connection between the hart Communicator and the positioner using the
2-pole communication line
3. Use the key [] to switch on the device the display indicates for several seconds that a
sell-test is in progress
warm start is executed which you must acknowledge by pressing the function key [Ey
If you are connecting your hand-held communicator to a field device for the fit
The display shows the base menu of the Type 3780 Positioner indicating online opera-
EB 8380-3 EN 3
Operation
2.2 Menu and ke
ey description
A maximum of five menu items can be displayed in numbered display lines. To access
urther menu items, press the [l key or directly enter the line number [1] to [9] on the alpha
numeric keypad
Since the line numbers can only be displayed as one-digit numbers, menu items above9are
marked by and can be accessed via the [] key onl
In addition to the Main menu there are further submenu levels in which data can be upda
ted. An updated menu item is displayed reversely in the display line an behind the li
number signifies that the next menu level can be accessed by pressing the [] ke
The labels located directly above the function keys show that key s software function, such as
1, for the current menu. to acknowledge an activated function
press the function key [f1 l to [F4] that is located directly below the activated label
For example, in menus providing access to online help, the
label appears above the
[F1] key. To view large texts that cannot be displayed entirely press[ ]or
to terminate hel
Alphanumeric keys [1] to [91
For direct selection of individual menu items(display line number), and for entering numerals
Arrow keys
For data input, you must first press the corresponding arrow key to select one of the left, cen
ter or right letters or other symbols before you press the corresponding alphanumeric ke
2.3 Data entry
Fields in which you can enter data are displayed reversely and the relevant digit position
blinking. You can access the digit position with the [ and [e] key and delete it with the
function using the corresponding function key. Use[ to leave the field unmodified
without accepting the entered data. to store the entered data, select
1, to leave the current input field, and[ to go to the previous field. Using
brings you back to the Online menu
Note
For more detailed information on the input fields, use the [F1] key to enter[HELP]
To obtain a list and description of the variables, refer to the List of parameters in the
Mounting and Operating Instructions EB 8380-1 EN
4833EN
Operation
3780:/
ne menu
Online
48.5
%
Previous menu
XI menu
48.4
%
0.1
%
\5 Information
Dynamic labels-HELP
F1
ncTIon keys
ommunicator On /OFf
6合》
Zero adjustment
Action ke
ecIous menu
Next menu
Step de
Alphanumeric keys
ABCIIDEFIIGHI
入89
凵凵
Shift keys
Confiquration and initialization
2. 4 Configuration and initialization
The positioner is supplied with a basic configuration containing the default values (coldstart
values). These settings or other potentially existing configuration data can be overwritten by
entering a new data record
note!
The inner side of the hinged lid contains a slider for write protection
When in position 1, the settings of the positioner are write-protected and cannot be overw rit-
ten by the hart protocol
To enable the hand-held communicator to overwrite the adjustment data, the slider must be
set to o
Basically, you should begin with entering the tag number, plant identification number as well
as the current date in the menu
to make them
available to the positioner
The manufacturers actuator and valve identification number as well as the actuator type
linear or rotary actuator)and attachment (integral positioner attachment or according to
NAMUR)must then be entered in the menu
Finally, you can enter the desired operational data in the menus
If you intend to use the positioner in split-range mode, you must change the polling addre
in the menu
from 0(default)to 1 for the first valve
or from o to 2 for the second valve
Finish configuration by starting the initialization procedure for the positioner in the menu
6833EN
Configuration and initialization
2. 4. 1 Configuration example
the Type 3277 Actuator, connected to associated positioner over point-to-Point ing, e ano
Based on the SAMSoN Type 3241-7 Control Valve, consisting of the type 3241 val
Positioner version includes two software limit switches
The sequence of the concise description given below can be clearly seen with the help of the
menu structure in chap 3. 1. From within the Online menu you can access the different sub
menu levels via the line numbers
Deli
ly air to the positie
nd connect to the referer
able >4 mA
Establish connections and switch on the hArt Communicator
The connected positioner appears on the display in the Online menu
keys [2], [1l, []in succ
enter the tae
ber in the input field
Confirm with function key [F4]
Press key [5] to enter the plant identification number under
Confirm with function key[氏F4]」
ress ket
ent date unde
]. Confirm with function key [F4j.
Press keys [E], [2], [2] to enter the manufacturers actuator identification number under
firm with function key [f4]
Press key [3] to enter the manufacturer's valve identification number under
]. Confirm with function key [F4]
Press keys [G1,[31, [3] to enter O under[
Confirm with Function key [F4]
key [F3] for[ to return the Onlin
Press keys [4],[11, I1l, [1] to select the linear actuator under
Confirm with和 unction key[F4]」
Press key [ F3] for[ to return the Onli
ne menu
Press keys[4], [21, [11, [1] to enter the start value of the reference variable (4 ma)under
]. Confirm with function key [F4]
Press key [2] to enter the end value(20 mA)of the reference variable under
Confirm with function key [e4]
Press keys [el, [2] to select the operating direction(>)under
Confirm with function key [F4]
Press keys [3], [1l to adjust(1%)
Confirm with function key [F4]
Press key [2] to adjust(125%under
Confirm with function key [F4]
Confiquration and initialization
Press keys [e] [4], [1] to enter the start value(0.0
mm unde
Confirm with function key [F4]
Press key [ 2] to enter the end value(15 mm) under
Confirm with function key [f4
Press keys[61, [51, [1] to enter the desired travel limit(0.0 %)under
Confirm with function key [F4].
Press key [2] to enter the desired travel limit (100 % under
Confirm with function key [F4]
Press keys[e1, [6], [1] to adjust
I by retaining the value 0.0 s or
changing it as required. Confirm with function key [F4].
Press key
by retaining the value 0.0 s or changing
it as required Confirm with function key [fa]
Press keys [e1, [7], [1l, for error monitoring
retain 5% or change it as re
quired. Confirm with function key [f4
> Pr
o adjust
by either retaining 10 s or changing it as requi-
red. Confirm with function key [F4]
Press keys [e1, [8] to adjust
1. Confirm with function key [F4].
Press key [9] to use [ 1l, [2 [3] to choose the desired fault alarm functions by entering yes
or no ConFirm with function key [F4].
Press keys[e1,[v], [- to adjust the operating direction (>>)for the position transmit
Confirm with function key [f4].
Press keys [], [11, [1] to adjust
for the lower limit value
GWI. Confirm with function key [F4].
Press key [2] to choose <=fall below, or >= exceed under[
Confirm with function key [F4]
Press keys[←[→],[2],[] to adjust
For the upper limit va-
ue Gw2 Confirm with function key [f4
Press key [2] to choose>=exceed, or <=fall below under
ith function key [F4]
Press key [F3] for[ to return to the Online menu
Press keys [4], [31, [1] to select a characteristic. Default is linear, if needed, select another
characteristic
Confirm with function key [F4]
8 EB8380-3EN
Configuration and initialization
Important
The valve characteristic is determined by the geometrical shape of the seat and plug. Ent rie
you make in[ Characteristic]modify the valve's characteristic so that there is a resulta nt of
both characteristics
You can switch between linear and equal percentage, equal percentage reverse and user-de
When you select an equal percentage characteristic, it is copied into the user-defined
characteristic, overwriting any previously entered user-defined characteristic!
For a user-defined characteristic, you can enter optional coordinates via 1 1 paired values
reter qlso
to table)
Press key [F3] for[ to return to the online menu
Input and output values in
Point
X
o00000.0000.000
1010.11.68.6177105
2|2520.24419.631418.4
34630.26.023.950230.9
7840212233.6655438
5]12.550.215938872.650.7
6]19560.2‖33.655.1787582
729.7070.2
664.390.6757
18]44880.163675293581.3
9]671900816861%1879
10]1001001000100010
Examples Equal percentage SAMSON butter fly valve
Add further user-defined values here
Linear
Equal percentage
The table lists the coldstart values for the user-defined characteristic equal percentage reverselin the first double
column. the following double columns show user-defined values, e.g. for a Samson butterfly valve
9
Confiquration and initialization
Press key
[4], [4] to access the parameters menu
We recommend that you retain the default settings, since they suffice most applications
Press key 1] to enter the proportional-action coefficient for supply air under[ I
Retain
ith[F4]
Press key [2]
-action coefficient for exhaust air under[ 1
Retain the default value 1. 20 or change it Confirm with [F4].
Press key [3] to enter the gain factor under[ ] retain the default value 0. 12 or change
it. Confirm with [F4
Press key [4] to enter the dead band under[ ] Retain the default value 0.5 or chan
ge it. Confirm with [F4].
Press key [5] to enter the overshoot under
1. Retain the default value 0.5
or change it. Confirm with [F4]
Press key [6] to select pulse adaptation to be
J or disabled. Confirm with
[F4].
Press key [F3] for[ to return to the Online menu
Data input has been completed
Now start the initialization routine for the
posITioner/valve assem
10EB83803EN