文件名称:
葆德11系列变频器操作指导手册(英文).pdf
开发工具:
文件大小: 4mb
下载次数: 0
上传时间: 2019-10-11
详细说明:葆德11系列变频器操作指导手册(英文)pdf,葆德11系列变频器操作指导手册(英文)INTRODUCTION
This manual contains installation, operation, maintenance, and troubleshooting instructions
for the BALDOR Series 11 P.W. M. style inverter drives for the range of 1 through 5
horsepower, 200-230 VAC. A parts list and illustrations are also included. For more
information on how to size these units to particular applications, please refer
BALDOR Inverter Applications Manual
GENERAL DESCRIPTION
The BALDOR Series 11 adjustable frequency Ac drives are designed to provide adjustable
speed control of conventional three phase induction motors. The method of control is
accomplished by a static conversion of the fixed frequency single or three-phase AC supply
into an adjustable frequency adjustable voltage output to the three-phase induction motor
These microcomputer based Pulse Width Modulated(WM)inverter drives have standard
adjustment features that allow tailoring of the motor/inverter system to fit a wide variety of
application requirements including variable torque, constant torque, andconstant
horsepower applications
MOTORS
Either one of the following two basic motor categories can be used with the BALDOR
family of inverter drives
1. Any standard three-phase AC induction motor designed to operate at standard line
frequency and fixed speed operation (speed determined by the load applied to the
motor) provided the following natural occurrences are considered
a. A slight increase in motor losses will occur when operated on a power source with
subharmonics in the output power wavEiorm. All motor controllers that
approximate a sinewave by electronic switching of a DC source will have
subharmonics present in the output power waveform
The motor' s capabi
to produce continuous torque(typically NEMA rated torque
at rated motor horsepower) must be derated as a function of the minimum
continuous operating speed due to the reduced ventilation of the integral motor
cooling fan. Where applications require 100% rated motor torque(constant torque
application) at speeds below half rated speed, a separately powered constant air
flow ventilation blower should be considered
When a separately powered
ventilation blower is used, a temperature sensing device should be built into the
motor and connected to the control wiring to shut the motor down whenever an
over temperature condition exists within the motor
CAUTION: An automatic reset device should never be used in cases where
an automatic restart of the motor could cause personal injury or
harm
C. Motors that will be operated above nameplate speed should have special
consideration for mechanical suitability of the motor. Special consideration of the
bearings, rotor balance, internal cooling fan construction, etc. may be needed.
Please consult the motor manufacturer for more specific details on your particular
type of motor and application requirements
d. Motors that will be controlled by a PWm style inverter operating from a 460 VAc
RMS power source will require special insulation between adjacent coil windings
phase insulation) within the motor to prevent phase to phase shorts. By the
nature of the power conversion within the PWm controller, the motor terminals will
see approximately 650 VDC peak. This elevated voltage level will eventually cause
phase to phase shorting within the motor if proper precautions are not taken
2. Any three-phase induction motor specifically designed for adjustable speed operation
by an inverter type of motor control
MODEL TYPES
The BALDOR Series 11 inverter drives are available in horsepower ratings from 1 through
5 HP and various input voltages as shown in Table 1. the controllers are available in open
chassis form for mounting into existing control cabinets and OEM use. The enclosed
versions carry a NEMA 1 enclosure rating and are equipped with three knockouts suitable
for attaching standard 3 /4 inch conduit fittings. Optional NEMA 4 and NEMA 12 enclosures
are available through your local BALDOR stocking distributor.
All BALDOR Series 11 inverters are complete functional motor speed controllers requiring
only fused input power and a suitably sized three-phase AC induction motor to form an
adjustable speed drive system. Remote operation and computer control are available by
the addition of external control devices and connection to the onboard control terminal
strip
5
TABLE 1. MODEL MATRIX
MAXIMUM OUTPUT
AVAILABLE CONFIGURATIONS
BRAKE
MODEL
INPUT V
CAPACITY CURRENT HORSEPOWER CHASSIS NEMA 1(TORQUE)
D11201
750W
5A
(100%)X
X
(100%)X
D11202
2
150oW
7A
2
X
(100%)X
23
X
(100%)X
D11203
VAC
2200w
11A
(100%)Ⅹ
3-g
X
(100%)Ⅹ
D11205
3700w
15A
(70%)X
(70%)X
All 230 VAC Series 11 inverter drives are suitable for use on 230 VAC single-phase input
power provided that the drives are derated per Table 2
TABLE 2-230 VAC SINGLE-PHASE DERATE SCHEDULE
SINGLE PHASE INPUT RECOMMENDED 3-PHASE MODEL
REQUIRED LOAD HP
LIGHT LOAD
HEAVY LOAD
1/2HP
1 HP
2 HP
1 HP
2 HP
3 HP
2 HP
3 HP
5H
3 HP
5 HP
7.5HP
Light Load: Fans, Blowers, Centrifugal Pumps, etc
Heavy Load: Conveyers, Mixers, Agitators, etc
6
CONTROLLER IDENTIFICATION
All Series 11 inverter drives have a nameplate attached to the drive indicating model
number, applicable controller ratings, and a manufacturing date code. On enclosed units,
the nameplate is located on the left side of the enclosure housing. For bare chassis units
the nameplate is located on the transistor heatsink just below the control terminal strip. to
determine the controller rating from the inverter model number, please refer to Table 3
TABLE 3- MODEL IDENTIFICATION
D 11205-E B(EXAMPLE)
BRAKE CODE
B-REGENERATVE BRAKE RESISTOR
OMIT IF NO BRAKE
ENCLOSURE CODE
E-ENCLOSED NEMA 1 HOUSING
c- CHASSIS MOUNT ONL丫
HORSEPOWER CODE
01-1HP
02-2HP
03-3HP
05-5HP
07-75HP
10-10HP
VOLTAGE CODE
2-230VAc顶
4-460VAc3小
SERIES 11 FAMILY
BALDOR INVERTER DRIVE
RATINGS
1. Horsepower·.……
1/2 through 5 HP 200-230 VAC 10
1 through 5 HP 200-230 VAC 30
2. Input Frequency
50 or 60 Hz
3. Output Power (Three Phase)
A. Voltage
鲁■香自·。鲁
0 to Max Input VAC
B. Frequency(Standard Range
0 to 60 Hz
(Programmable Option)
0 to 120 Hz
4. Service Factor
1.0
5. Duty
Continuous
6. Overload Capacity(Rated Current
150% for 120 Seconds
200% to Trip on Overcurrent Fault
7. Frequency Setting(Standard Range)
.....0to+5VDc
8. Frequency Setting Potentiometer
5K,1/2W
OPERATING CONDITIONS
1. Input Voltage Variation
+/-10%
2. Input Frequency Variation
+5%
3. Ambient Temperature
a. NEMA 1 Enclosure
10to+40°
b. Open Chassis
·鲁着
10to+50°C
4. Humidity
90% Max RH Non - Condensing
5. Altitude
3300 Feet Max Without Derate
SPECIFICATIONS
1. Control Scheme
Sinewave Carrier Input, PWM Output
2. Frequency Accuracy
..+/0.5%25°0+/-10°C
3. Frequency Resolution
0.24Hz6OHz,0.48Hz120Hz
4. V/F Pattern
Linear to Squared Reduced in 101 Steps
5. Base Frequency
30 to 250Hz in 221 Steps
6. Carrier Frequency ..,
868 to 1420Hz in 8 Steps
7. Torque Boost
0 to 30%of Input Voltage in 101 Steps
8. Output Voltage
0 to Input voltage in 101 Steps
9. Accel Decel Time
0.1to1400Sec60Hz;0.1to2800sec120Hz
10. Braking Torque
20%Min . 70 to 100%With Braking Resistor
11. Dynamic Braking Time
0 to 24. 8 Seconds
12. Jog Frequency
o to 30Hz
13. Upper Frequency Limit
0 to Max Frequency
14. Lower Frequency Limit
0 to Max Frequency
15. Skip Frequency
0 to Max Frequency in 2 Independent Zones
6. Operation Modes
2 Speed, 4 Speed, External Thermal Trip
STANDARD FEATURES
Fault Trip Indication: Whenever an appropriate internal or external situation exists to
cause a fault condition within the inverter, the inverter output will be shut off and an open
collector transistor at control terminals 1 and 2 will conduct to give an external indication
of the fault occurrence. A visual indication as to the type of fault will be shown via fault
codes on the led display located on the front panel of the inverter a red LEd located on
the lower right hand side of the inverter main circuit board will illuminate to indicate a fault
condition. the open collector transistor has a maximum input voltage of 24 Vdc and a
maximum current carrying capacity of 50 maDC. A trip condition can be reset internally
by momentarily pushing the reset button or externally by commanding Forward and
Reverse movement simultaneously.
Instantaneous Power Failure Protection (Auto Restart): The inverter output will be shut
off if the dc bus of the converter section drops below 61% of normal for more than 15
mSec. If input voltage is restored before the end of 15 mSec. the inverter will resume
normal operation from the frequency specified by the Reduced Frequency At
Instantaneous Power Failure parameter. When input voltage is reduced below 61%but
still greater than 46% of normal for more than 15 mSec. the fault trip circuit will be activated
and the open collector transistor at control terminals 1 and 2 will conduct to give an
external trip indication for lack of input voltage
If the input voltage is reduced below 46%of normal or removed and then reapplied with
the RUN/STOP switch in the RUn position and the selection of manuallauto restart
parameter is set at", the inverter will start the motor as if a run command has been
initiated. This command sequence is known as auto Restart and no external trip indication
will be given
CAUTION:
If an automatic restart of the motor could cause personal injury
or harm. the Auto restart function should be defeated
Overcurrent Trip: The inverter output will be shut off when the output current of the
controller exceeds 200% of rated current. The fault trip circuit will be activated and the
open collector transistor at control terminals 1 and 2 will conduct to give an external trip
indication
External Thermal Trip: The inverter output will be shut off whenever an open circuit
condition exists at control terminal 10 with respect to control terminals 5 or 8. Closing this
circuit is usually accomplished with an externally mounted normally closed thermostat. The
fault trip circuit will be activated whenever an open circuit is sensed, then the open collector
transistor at control terminals 1 and 2 will conduct to give an external trip indication. The
External Thermal Trip function will only operate when the inverter is in the External Thermal
Trip mode of operation
Regenerative Overvoltage Trip: The inverter output will be shut off when the voltage of
the dc bus is higher than 23% above normal. The fault trip circuit will be activated
whenever an overvoltage condition exists on the DC bus. The open collector transistor at
control terminals 1 and 2 will conduct to give an external trip indication This type of fault
condition is usually due to an overhauling load on the motor output shaft during periods
of deceleration causing the motor to regenerate energy back into the motor controller. This
trip condition can usually be corrected by extending the deceleration time
Overvoltage Stall Prevention: During periods of deceleration the decel time will be
extended whenever an impending Regenerative Overvoltage trip is sensed. Total decel time
will be multiplied by the value set by the Stall Decel Magnification parameter whenever
an impending Regenerative Overvoltage trip is sensed. The total decel time with
Overvoltage Stall Prevention is the product of (Decel Time)X (Decel Magnification) X(Stall
Decel Magnification)
Self Diagnosis Trip: The inverter output will be shut off and the open collector transistor
at control terminals 1 and 2 will conduct to give an external trip indication when any of the
following occur
a. A malfunction of the microcomputer is detected
b. The inverter will trip for safety whenever the max output frequency is changed
c. The inverter will trip for safety whenever a change is made to the operation mode
Digital Display: A digital display is mounted to the front of the inverter to give a visual
display of set-up parameters, operation mode, output frequency, and fault diagnostics
Controlled Reversing: The motor shaft rotation can be reversed by shorting control
terminal 9 to terminal 5 or 8. the shorting of the control terminals is usually accomplished
by an external switch closure. The ability to electronically reverse the motor shaft rotation
eliminates the need for external reversing contactors. When a controlled reversal is
commanded, the motor will dec alerate down the decel ramp to zero speed and then
accelerate up the accel ramp in the reverse direction
us Voltage Present Indicator: A red LEd is I cated on the lower left hand side of the
ir. erter main control board. this LEd is used o give a visual indication that voltage is
present on the DC bus. When voltage is present on the dC bus the LEd will illuminate
CAUTION: Do not rely on the Bus Voltage present indicator to determine
when the unit is safe for maintenance or service. Always wait at
least 5 minutes after disconnecting input power before beginning
any internal servicing of this equipment.
Regenerative and DC Dynamic Braking Motor braking is available for stopping or short
duration holding. The standard braking torque is 20% of the motor's full load torque. Units
equipped with a braking resistor have an available braking torque of 70 to 100%of the
motor's full load torque
10
Adiustable skip Frequencies: Two fully adjustable frequency skip zones are available to
minimize mechanical resonance. In some applications certain inverter output frequencies
may cause a mechanical resonance to develop in the driven motor load, By skipping these
inverter output frequencies the machine mechanical resonance may be avoided. The
frequency skip zones are selected by specifying the continue frequency and the jump
frequency.
Selectable 4 Speed Operation: Two modes of operation available from the BALDOR
Series 1 1 is a selectable 4 speed mode. One of 4 independent speeds is selected by
appropriate external switch closures connected to the inverter control terminals 10 and 11
with respect to control terminals 5 or 8. Other operation modes include 2 Speed Operation
and External Thermal Trip.
Independent Accel/Decel Rates: Each selectable speed has an independent accel/decel
rate adjustment. The time of accel will equal the time of decel for each selected speed
The rate of decel for a Stop command is independent from all other accel/ decel rates. The
actual rate of accel/decel is the product of(Accel Decel Time)X(Accel Decel Magnification)
Actual stopping time may vary depending on the inertia of the driven load
ADJUSTMENTS
Base Frequency: The Base Frequency parameter sets the point on the V/F curve where
the voltage output of the inverter becomes a constant value with increasing output
frequency. The base frequency is adjustable within the range of 30 to 250 Hz in 221 steps
Carrier Frequency: The PWM carrier frequency input to the internal inverter control
scheme is adjustable within the range of 868 to 1420 Hz in 8 steps. The PWM carrier
frequency can be adjusted to minimize audible noise
Volts/Hertz VF)Ratio: The BALDOR Series 1 1 has a fully adjustable v/F ratio. The V/F
ratio is set from the factory to be a linear function for constant torque applications and can
be adjusted to a squared reduced relationship for variable torque applications. The Base
Frequency parameter can be adjusted to give constant horsepower from a properly sized
AC induction motor throughout the entire speed range
Maximum Output Frequency: The maximum output frequency is set from the factory at
60 Hz. The maximum output frequency can be set to 120 Hz via a dip switch located on
the lower right hand side of the main control board to allow the motor to be driven at twice
the motor's rated speed. Please consult the motor manufacturer for suitability to run at a
speed higher than the nameplate rating
Upper And Lower Frequency Limits: The upper and lower frequency output of the motor
controller can be set to limit the adjustable speed range of the driven motor. This feature
is useful in application where a minimum or maximum motor speed is desired regardless
of the input command signal
11
(系统自动生成,下载前可以参看下载内容)
下载文件列表
相关说明
- 本站资源为会员上传分享交流与学习,如有侵犯您的权益,请联系我们删除.
- 本站是交换下载平台,提供交流渠道,下载内容来自于网络,除下载问题外,其它问题请自行百度。
- 本站已设置防盗链,请勿用迅雷、QQ旋风等多线程下载软件下载资源,下载后用WinRAR最新版进行解压.
- 如果您发现内容无法下载,请稍后再次尝试;或者到消费记录里找到下载记录反馈给我们.
- 下载后发现下载的内容跟说明不相乎,请到消费记录里找到下载记录反馈给我们,经确认后退回积分.
- 如下载前有疑问,可以通过点击"提供者"的名字,查看对方的联系方式,联系对方咨询.