详细说明:艾默生-Chloride10-20K_通讯协议I/P frequency:
RRR
R is an integer number ranging from 0 to 9. The unit is Hz
Battery cell volt
S SS
age:
S is an integer number ranging from 0 to 9
Temperature
TTT
T is an integer number ranging from 0 to 9. the unit is degree of cen-
tigrade
UPs Status:
b7b6b5b4b3b2b1b0
Where is a binary number,o or m1
UPS status
Bit
Description
1: Utility Fail( immediate
1: Battery Low
1: Bypass/ Boost Active
1: UPS Failed
1: UPS Type is Standby(o is
On_line
1: Test in Progress
1: Shutdown Active
Reserved (always)
Stop Byte:
≤cr
The binary code is modified to 8 bytes aSCIi code for avoiding the
binary code confused with ASCIi control code.
Between each data stream add one space for the data separation
Example:
Computer: Q1
UPS:
(208.4140.0208403459920535000110000
Means: I/P voltage is 208.4 V
I/P fault voltage is 140.0 V
O/P voltage is 208, 4 V
O/P load is 34%
I/P frequency is 59.9 Hz
Battery voltage is 2.05 V.
Temperature is 35.0 degrees of centigrade
UPS type is on-line, ups failed bypass active and shutdown
not active
Status inquiry 2 command:
Computer
Q2
UPS:
MMM M MMM.M MMM,M NNN.N PPP.P PPP.P PPP.P QQQ QQQ
QQQ RR,R SSSS TT. b7b6b5b4b3b2b1b0 ttttt CCC BB ffff ff
ff wwwwwwww Yo
Input voltage:
MMMM
M is an integer number o to 9. The Unit is volt
3 Phase system three phases will represent Phaser, s, t in sequence
Split Phase system, three phases will represent phase R, s and rs in
sequence
I/P fault voltage: NNN. N
N is an integer number 0 to 9. The Unit is volt
Output Voltage:
PPP.P
P is an integer number 0 to 9. the Unit is volt
3 Phase system, three Phases will represent Phase R, s, T in sequence
Split Phase system, three Phases will represent Phase R, s and rs in
sequence
Output Current: QQQ
QQQ is a percent of maximum current, not an absolute value
3 Phase system, three Phases will represent Phase R, s, T in sequence
Split Phase system, three phases will represent phase r, s and rs in
sequence
I/P frequency
RRR
R is an integer number ranging from o to 9. the unit is hz
Battery voltage:
SSS.s
sis an integer number ranging from 0 to 9.
Temperature
TTT
T is an integer number ranging from 0 to 9. The unit is degree of cen
tigrade
UPS Status:
,
is a binary number n"or
JPS status
byte Description
1: Utility Fail( immediate
1: Battery Lo
1: Bypass/ Boost Active
UPS Failed
1: UPS Type is standby(0 is On_line)
1: Test in progres
1: Shutdown Active
Reserved (always 0)
Estimated
ttttt
Runtime
Estimated Runtime/Remaining Battery Backup time in ttt minutes
and tt seconds. These values will be defined by the s-Series UPS
Processor with High accuracy In comparison to the existing PowerPro
tect interfacing the p-Series there will be no internal algorithm neces
sary
Charge in Status CCC
O/
This values will be defined by the s-Series UPS-Processor with high
accuracy In comparison to the existing powerProtect interfacing the
P-Series there will be no internal algorithm necessary
ccording to our research and development results the battery capaci
ty can be improved by the special maintenance and cultivation of the
battery by the UPS. a charge status valued 100% therefore can be
the result
Provided range for the program
CCC=000.to,,133.
alues greater 133 will be shown as the maximum. values greater
than 100 will be displayed graphically with a full light bar column
(100%)and shown digitally as the received value <=133
Status of Battery BB
test
00 idle
01 processing
02
result no failure
03 result: failure /warning
04 Not possible or inhibite
05 Test cancel
06 Reserved
07 Other values
Fault code
ff
The protocol has 4 fault containers which could be filled simultaneous
ly. The range of fault numbers covers from 32 to 99. E. g
00 41 5578 means for each container a certain fault message( in
00- INVERTER-BYPASS-OTHERS
a text file which will contain 100 lines will represent all Faults and
Warnings
PowerProtect should show the fault number and message text as one
line for each container(more see chapter 3)
Warnings
11111111111111111111111111111111
2725.202
28223.216
224
Bit0(2 0)represents Warning 1
Bit7(2 7) represents Warning 8
Bit 31 (2 31)represents Warning 32
Theoretically each of the 32 warnings could come up, wed like to limit
the number of simultaneous displayed warnings to 6
Shown example:
WWWWWWWW=00160000(hex)
=00000000001011000000000000(bin
2726.2021528223.21
2
24
warning 8-1 warning 16-9 warning 24-17 warning 32-18
Mean warning 10, 11, 13 then find the warning table
nput transformer Y
type:
Y is a binary number ,Oor m1
Input transformer Delta or Y
Y=1, Input transformer is y type lcd display phase voltage
Y=0, Input transformer is Delta type lcd display line voltage
Lcd Display out
put Voltage Line
or phase:
o is a binary number ,o or 1
LCd display output voltage Line or phase
o=l, lCd display output voltage is Phase
0=0, LCD display output voltage is Line
If o=1 (Phase voltage), but monitor software want to display line
voltage
Line voltage=√3× Phase voltage
If 0=0(Line voltage), but monitor software want to display phase
Voltage
Phase voltage= Line voltage /3
Stop Byte:
Who am i command:
Computer
WH
UPS:
OX VV. VV PP, PP TTTTTTTTTTTTTTTTTTTTTTTTTTTTTT W MMM
FFFF WV SS. SS HHHhh GGG. gg RRR mm nn MMM NNN FF FF
FFFF
Slave Address
XX
(UPS ID):
X is an integer number ranging from 0 to 9.
UPS Firmware
Version
V is an integer number ranging from o to 9
For an ex: 09.90
Protocol number: PP PP
P is an integer number ranging from o to 9
For an ex: 03.30
UPS Name
TTTTTTTTTTTTTTTTTTTTTTTTTTTTTT(30 Char.
The first T called byte 0, the least byte called byte 29
Ps name will sequence from first byte 0
Byte 25 is means the input source
(Empty ): means only one input source
2. means two input sources(Bypass utility source and line utility
source), If get this character (2), pC side need add to send
the BPs command then get bypass utility data
Byte 26 is always empty
Byte 27, 28 and 29 definition as below
Byte27: means input phase number
Byte28 is always/
Byte29: means output phase number
ByteByte Byte
description
272829
1 Single phase input and single phase output
2Two phase input and two phase output
1 Three phase input and single phase output
3Three phase input and three phase output
Battery cell number: W
W is an integer number ranging from 0 to 9
Nominal mains
MMM
Voltage:
M is an integer number ranging from 0 to 9
Nominal mains
FFFF
Frequency:
F is an integer number ranging from o to 9
Number of Battery Vv
Cells in series
V is an integer number ranging from 0 to 9
Nominal cell volt- SS. SS
age:
S is an integer number ranging from 0 to 9
Hold time at
HHH hh
100%0Load:
H is an integer number ranging from 0 to 9.
HHH in minutes and hh in seconds
Hold time at 50%o GGG. gg
Load
G is an integer number ranging from o to g
GGG in minutes and gg seconds.
Recharge time to RRR
9500:
R is an integer number ranging from 0 to 9. The unit is hours
Minimum ambient mm
Temperature
mm is an integer number ranging from o to 9 the unit is oC
Maximum ambient nn
Temperature:
nn is an integer number ranging from o to 9. the unit is oc
Minimum mains
MMM
Voltage:
M is an integer number ranging from 0 to 9. the unit is volt
Maximum mains nnN
Voltage:
N is an integer number ranging from 0 to 9. the unit is volt
Minimum mains
FFFF
Frequency:
F is an integer number ranging from o to 9. the unit is hertz
Maximum mains FFFF
Frequency
F is an integer number ranging from 0 to 9. The unit is hertz
Stop Byte
KW and kva commande
Computer:
WA
UPS:
(www.wWwwwWww.w.Wv.vv.vw.Vttt.tSss.s
AAA. A AAA.A AAA, A QQQ b7b6b5b4b3b 2b1b0
The first of the UPS respond is very similar to the existing inquiry Q1
however
Output power:
Www.w
W is an integer number o to 9. the Unit is Kw
3 Phase system three Phases will represent Phase r, s, T in sequence
Split Phase system three phases will represent Phase r, s and rs in
sequence
Output complex
WW.
power
V is an integer number o to 9. the Unit is Kva
3 Phase system three phases will represent Phase R, s, T in sequence
Split Phase system three Phases will represent Phase R, s and Rs in
sequence
Total power:
TT.
T is an integer number o to 9. the Unit is Kw
3 Phase system, Include of three phase r, s, &t real power.
Split phase system Include of three phase s real power
Total complex
SSS S
power
S is an integer number o to 9. the unit is Kva
3 Phase system, Include of three phase rs, &t complex power
Split Phase system, Include of three phase R, s complex power
Output current
AAAA
A is an integer number 0 to 9. The unit is a. r phase
3 Phase system three Phases will represent Phase R, s, t in sequence
Split Phase system three phases will represent PhaseR, s and rs in
sequence
O/P load:
QQQ
QQQ is maximum of W% or VA%. VA% is a percent of maximum VA
W% is a percent of maximum real power.
UPS Status
b7b6b5b4b3b2b1b0
The same of Q1UPS status:
Stop Byte:
Inquiry bypass utility command:
Computer
BPS
UPS:
MMM.M MMM.M MMM. M FF. F
Bypass I/P Volt- MMM.M
age:
M is an integer number o to 9. The Unit is volt
In the single phase, Only R phase has the valid, s and t will always
get
In the 3 Phase system three phases will represent phase r, s, t in
sequence
Bypass I/Pfre
FFF
quency
F is an integer number ranging from 0 to 9. The unit is hz
Stop Byte:
10 seconds test command
Computer
T≤cr>
UPS
Test for 10 seconds and return to utility